Functions and features

The slave converts analogue input signals and transfers them to the
AS-i master via the AS-Interface. The AS-i module operates as a slave
with bidirectional data transfer in the AS-i network.
The data transfer to the host is asynchronous according to the AS-i
profile S-7.3.D and the AS-i specification 3.0, downward compatible.
• maximum number of modules per master: 31
• current measurement 4...20 mA
• time for converting the measured values in the slave
- for one channel: 60 ms
- for two channels: 120 ms
When the sensors are supplied from AS-i the load must not exceed a
maximum of 200 mA. There is an electrical connection between the
sensor and AS-i.

Operating and display elements

LED PWR
LED FAULT
labels
2 M12 sockets
Assembly
Notes on assembly from page 17.
addressing interface
LED 1
earthing lead
7