When done successfully, then the 3. Programming level is displayed
for change:
Now the sensor type can be changed
P = Pt100, F=Fe-CuNi, n=NiCr-Ni ,
individually via the two control buttons
(refer also to „Technical Data")
Warning:
The pre-installed bridge for Pt100 mode fools the controller with an installed
sensor and shows wrong temperature data, which can be analog to the envi-
ronmental temperature. If another sensor is to be installed, then the bridge
must be removed. Without the bridge the controller will show the correct error
code, if a wrong sensor has been installed acc. to the set programming.
5. Step:
Wait for ca. 20 sec. until the controller sets back automatically into working
level and starts with its initialization again (see pic D.)
The data have been adopted.
Indicating status – Display:

Alarm Out

(see also "Electrical Connection and Mounting")
NC:
Outlet 2.1
COM:
Outlet 1
NO:
Outlet 2.2
Normal-condition (ON): COM and NO
Alarm-condition (OFF): COM and NC
12
St - P
or
NC-Function
NO-Function
are closed!
are closed and heater is off!
St - F
or
St - n
(down) or
(up)
(normally closed)
(common)
(normally open)