Remote Maintenace With A Modem; Recommended Modems; Rs-232C Straight Cable Between Modem And Al2-Gsm-Cab - Mitsubishi Electric Al2 Série Manuel Du Propriétaire Du Matériel

Controleur
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 150
α
2 Simple Application Controllers
8.3

Remote Maintenace with a Modem

Further information of the modem setup procedures can be found in the
Manual. The programming software (AL-PCS/WIN-E) provides the easiest method to setup
the modem.
8.3.1

Recommended Modems

The following modems have been successfully tested.
Table 8.2: Tested Modems
Maker name
3com
OMRON
AIWA
Siemens
8.3.2

RS-232C Straight Cable Between Modem and AL2-GSM-CAB

Figure 8.5: RS-232C Straight Cable Reference Between a Modem and AL2-GSM-CAB
AL2-GSM-CAB Side
(9-pin D-Sub female)
1
2
3
4
5
6
7
8
9
Model name
SP560V-P
ATE0Q1&B1&D0H0&I0&R1&S0S0=2S15=8&W
ME3314
ATE0S0=2Q1&D0S15=8&R1&H0&W
PV-AF3360
ATE0S0=2Q1&D0&M5\Q0\J0&W
M20T
ATE0S0=2&S0;+IFC=0,0;+CMEE=1;+IPR=9600&W
Modem Side
(25-pin D-Sub male)
Modem command (AT command)
1
8
3
2
20
7
6
4
5
22
AL2-GSM-CAB 8
α
2 Programming
ENG-40

Hide quick links:

Publicité

Table des Matières
loading

Table des Matières