Wire Size - Mitsubishi Electric Al2 Série Manuel Du Propriétaire Du Matériel

Controleur
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 150
α
2 Simple Application Controllers
4.2

Wire Size

Wire of the Inputs and Outputs using the following wire. Strip the wire to the following length
(See Table 4.1 and Figure 4.1). Please unscrew the terminal to its widest position before
inserting a wire. Insert the wire completely into the terminal to ensure that a proper connection
can be made.
The terminals will accept a 3mm flathead screwdriver.
Table 4.1: Wire Size
Main Unit
Extension Module
Figure 4.1: Wire Size
Main unit
26 -12 AWG
7mm(0.276") ± 0.5mm(0.02")
Note;
• To avoid damaging the wire, tighten to a torque of 0.5 - 0.6 N⋅m.
• Please do not use tin, solder, or any other substance on the stripped wire that might
cause the wire strand to break.
- Stranded cable:
Remove sheath, twist core wires, then connect cable (or use a crimp terminal).
- Single cable:
Remove sheath, then connect cable.
Wire Size
26 - 12 AWG (0.13 - 3.31mm
24 - 14AWG (0.2 - 2.5mm
Strip Wire Length
2
7mm ± 0.5mm
)
2
6mm ± 0.5mm
)
Extension module
24 -14 AWG
6mm(0.236")
Wiring 4
ENG-18

Publicité

Table des Matières
loading