Mini Chiller
Model
HLR8Pd/Na-K
HLR10Pd/Na-K
HLR12Pd/Na-M
HLR14Pd/Na-M
Notes:
① The leakage switch is necessary for additional installation. If circuit breakers with leakage
protection are in use, action response time must be less than 0.1 second, leakage circuit must be
30mA.
② The above selected power cable diameters are determined based on assumption of distance
from the distribution cabinet to the unit less than 75m. If cables are laid out in a distance of 75m to
150m, diameter of power cable must be increased to a further grade.
③ The power supply must be of rated voltage of the unit and special electrical line for air-
conditioning.
④ All electrical installation shall be carried out by professional technicians in accordance with the
local laws and regulations.
⑤ Ensure safe grounding and the grounding wire shall be connected with the special grounding
equipment of the building and must be installed by professional technicians.
⑥ The specifications of the breaker and power cable listed in the table above are determined
based on the maximum power (maximum amps) of the unit.
⑦ The specifications of the power cable listed in the table above are applied to the conduit-
guarded multi-wire copper cable (like, YJV XLPE insulated power cable) used at 40°C and resistible
to 90°C(see IEC 60364-5-52). If the working condition changes, they should be modified according to
the related national standard.
⑧ The specifications of the breaker listed in the table above are applied to the breaker with the
working temperature at 40°C. If the working condition changes, they should be modified according to
the related national standard.
Leakage
Power Supply
V,Ph,Hz
220-240V,1Ph,50Hz
380-415V,3Ph,50Hz
Minimum Sectional
Switch
Area of Earth Wire
(A)
(mm
20
2.1
20
2.1
13
1.3
13
1.3
21
Minimum Sectional
Area of Power
Supply Wire
2
2
)
(mm
3×2.1
3×2.1
5×1.3
5×1.3
eries
)