2.3 Setup the UPS

Installation and wiring must be performed in accordance with the local electric laws/regulations and execute the following
instructions by professional personnel.
1)
Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid the
hazards of electric shock or fire.
NOTE: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the UPS's
maximum input current. Otherwise the receptacle may be burned and destroyed.
2)
Switch off the mains switch in the building before installation.
3)
Turn off all the connected devices before connecting to the UPS.
4)
Prepare wires based on the following table:
Model
Input
5K (S)
8 / 6
6K (S)
8 / 6
8K (S)
6 / 10
10K (S)
6 / 10
NOTE 1: The cable for 5K (S) and 6K (S) should be able to withstand over 40A current. It is recommended to use
10AWG/6mm² or thicker wire for safety and efficiency.
NOTE 2: The cable for 8K (S) and 10K (S) should be able to withstand over 63A current. It is recommended to use
8AWG/10mm² or thicker wire for safety and efficiency.
NOTE 3: The selections for color of wires should be followed by the local electrical laws and regulations.
NOTE 4: External battery wires must use reinforced insulation or double insulated wire.
Warning:
● For standard battery pack, there are one DC breaker to disconnect the battery pack and the UPS. But for other external
battery pack, make sure a DC breaker or other protection device between UPS and external battery pack is installed. If not,
please install it carefully. Switch off the battery breaker before installation.
NOTE: Set the battery pack breaker in "OFF" position and then install the battery pack.
● Pay highly attention to the rated battery voltage marked on the rear panel. If you want to change the numbers of the
battery pack, please make sure you modify the setting simultaneously. The connection with wrong battery voltage may
cause permanent damage of the UPS. Make sure the voltage of the battery pack is correct.
● Pay highly attention to the polarity marking on external battery connector and make sure the correct battery polarity is
connected. Wrong connection may cause permanent damage of the UPS.
● Make sure the protective earth ground wiring is correct. The wire current spec, color, position, connection and
conductance reliability should be checked carefully.
● Make sure the utility input & output wiring is correct. The wire current spec, color, position, connection and conductance
reliability should be checked carefully. Make sure the L/N site is correct, not reverse and short-circuited.
2-4. Parallel UPS Installation
For parallel UPS installation, please refer to the annex 1 at the end of the manual.
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr –
Wiring spec (AWG/mm²)
Output
8 / 6
8 / 6
6 / 10
6 / 10
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
Battery
Ground
8 / 6
10 / 6
8 / 6
10 / 6
8 / 6
6 / 10
8 / 6
6 / 10
05 16 AA 59 205 03XX XX XX XX XX
9