Installation And Hook-Ups; Preparing The Installation Site; Air Ventilation Connections; Non-Standard Installations - Sime ECOMAXI 90 ErP Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation, use and maintenance manual
5

INSTALLATION AND HOOK-UPS

WARNING: the product must be installed,
commissioned
authorised, qualified personnel. Do not
attempt
to
install
yourself.
5.1

Preparing the installation site

The product must be installed in a suitable place,
where the normal use and adjustment operations
can be performed, as well as routine and non-
scheduled maintenance.
The necessary operating space must be prepared,
making reference to the measurements shown in
Fig. 3.
Wall-mounted, 90-
litre model
Fig. 7 – Clearances
Wall-mounted
X1
model
mm
Standard 90-litre
300
The space must also be:
equipped with suitable water mains and
electricity supply lines;
equipped with suitable water outlets in case of
damage to the boiler, the safety valve being
tripped or breakages in the pipework or
connectors;
equipped with any containment systems in
case of serious water leakages;
sufficiently lit.
5.2

Air ventilation connections

For the heat pump to work correctly, it requires
adequate air ventilation.
Create a specific air duct as shown in the figure
below (Fig. 4).
and
maintained
by
the
product
by
X2
Y1
Y2
mm
mm
mm
300
200
400
Con
necti
on
type
Con
B
necti
on
type
A
Outsi
Outsi
de
de
Fig. 8 – Possible air outlet connections
To ensure the heat pump is correctly ventilated,
the clearances indicated in section 5.1 must also
be respected.
Install the air duct making sure that it:
does not weight down on the appliance itself;
allows for maintenance work;
is
suitably
protected
accidentally getting inside the appliance itself;
does
not
exceed
recommended length of 6 metres (Ø125 mm
pipe with 2 x 90° elbow unions).
During operation, the heat pump tends to
lower the temperature in the room if the air
is not ducted.
A suitable protective grille must be installed
where the air outlet pipe connects with the
outdoors, to prevent foreign bodies from
entering the appliance. To guarantee
maximum product performance, the grille
must be a low load-loss model.
5.3

Non-standard installations

One of the unique features of heat-pump
heating
systems
considerable drop in the temperature of the
air usually expelled outdoors. The expelled air,
in addition to being colder than the air in the
environment, is also fully dehumidified. For this
reason, the flow of air can be fed back inside
the building again to cool rooms or spaces in
the summer.
A dual air outlet pipe is installed, with two
dampers attached (A and B), so as to be able
to direct the air flow either indoors (Fig. 5a) or
outdoors (Fig. 5b).
MANUAL CODE: 6328406
to
avoid
material
the
maximum
is
that
they
create
Page 40 / 124
a

Publicité

Table des Matières
loading

Produits Connexes pour Sime ECOMAXI 90 ErP

Ce manuel est également adapté pour:

8115800

Table des Matières