When installing the underground tanks of the Columbus series as collection tanks without a run off
system, all of the above assembly and installation instructions must be observed and followed and only
the connection/installation of the run off and the protective pipes are omitted.
Odour trap: In addition to the rubber seal on the telescopic attachment there is also an optional rubber
seal for the double walled PE cover which prevents odour escaping (Type - No.: 790079).
The entire system must be checked for leaks, cleanliness and stability at least every three months.
The entire system should be serviced at intervals of approx. 5 years. In this case, all parts of the system
must be cleaned and their function checked. Servicing should be carried out as follows:
Drain the tank completely
Remove any solidified sludge, dirt etc with a non-metallic scraper.
Clean surfaces and internal parts with water
Remove all dirt from the tank
Check that all internal parts are firmly seated