Replacing the flow restrictor
The KEMPER HS2 hygiene Flushing Box is
factory-fitted with a flow limiter to restrict
the flow to 10 l/min. By replacing the flow
restrictor, the flow can be limited to 4 l/
min or 15 l/min.
1
Remove the cover plate.
2
Remove the control unit.
3
Remove the solenoid valves.
4
Remove the filter screen and flow
limiter.
10 l/min
blue
blau
bleu
blauw
Maintenance Manual KHS HS2
5
Replace the flow limiter
(Art.-No. 6899900100)
and install the filter screen.
6
Use a ballpoint pen to note the new
value of the flow restrictor on
the sticker on the control unit.
hs2app.kemper-olpe.de
10 l/min
7
Install the solenoid valves.
8
Install the control unit and check the
solenoid valves for correct functioning.
9
Replace the cover plate.
10
EN
4 l/min
15 l/min
grey
green
grau
grün
gris
vert
grijs
groen
Kemper HS2 App
4 l/min
15 l/min