Installation and Operation Manual
7.
Control and indicator elements
7.1.
Toggle switch
Position 'T'
Postion 'T' activates the calibration process. The LED 'AlarmT'
respectively 'AlarmR' light up simultaneously for the duration of the
calibration. During this time, the protected area must be clear. If
defect or covered elements are detected, the number of elements is
shown by either the AlarmR LED flashing for receiver elements or
the AlarmT LED flashing for emitter elements. For example: If the
LED AlarmT flashes three times after calibration, three of the emitter
elements are either covered or defective.
7.2.
LED - Indicators
Power
Internal 5 V ok
SigOut
Relay on (short flash = self test ok)
SigIn
Input status of SigIn (on = high)
on = high (must be "high" during operation)
AlarmR
Diagnostic-LED receiver edge
AlarmT
Diagnostic-LED emitter edge
Description
The light curtain carries out a calibration cycle. It controls the intensity
of the emitter in a way that the receiver has a defined signal. The
length of calibration is between 1 and 5 seconds.
Alternating flashing of LED's AlarmR and AlarmT indicate a self test
at power up (appr. 10 seconds)
© CEDES/July 2020
Pos '0'
Normal operation .
Buzzer off.
www.cedes.com
cegard/Lift LI
Pos
Buzzer activated, as
soon as light curtain is
interrupted.
LED Symbols
LED off
LED on
LED not relevant (on / off)
LED flashes
7