afriso Flow-Control Mode D'emploi page 41

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

6
Operation
6.1
Pressure mode
Tanks mounted up to 4 m higher do not affect the function of the product. Use
protection equipment against siphoning (anti-siphon valve) in the suction line.
If a de-aerator is required in a pressure system, suitable safety-related equip-
ment must be installed so the the maximum permissible inlet pressure of 0.7
bar cannot be exceeded.
Use Flow-Control 3/K HT with an upstream filter and a brass filter cup as a
de-aerator.
6.2
Liquid level in the float housing
The liquid level depends on the operating conditions of the system and
amounts to approximately 20-50 mm in suction mode. If the liquid level is
higher, the float housing may be completely filled with fuel. When the operat-
ing conditions change, for example, decreasing liquid level in the tank, the air
cushion is formed again in the float housing.
6.3
Use in flood hazard areas
INOPERABLE PRODUCT
Verify that the product (without vent hose) is replaced after a flood.
Failure to follow these instructions can result in equipment damage.
With a connected vent hose, the product is suitable for use in flood hazard
areas; it is watertight up to 10 mH
The product with vent hose continues to be operative after a flood.
 Verify that the end of the vent hose is located at the return connection of
the tank or ends above the maximum possible water level.
Operation
NOTICE
O (1 bar pressure).
2
Flow-Control
EN
18