lISt Of paraMeterS tO Be dISplayed (fuNCtION 3)
Option recognition table
Decimal
Hexadecimal
address
address
256
100
257
101
258
102
259
103
NB: if several options are used, the number corres-
ponding to the option must be added.
lISt Of paraMeterS tO Be dISplayed Or prOGraMMed (fuNCtIONS 3, 6 aNd 16)
Decimal
Hexadecimal
address
address
512
200
513
201
514
202
515...518
203...206
519
207
520
208
521
209
No. of words
Text
1
0 : no option
1 : metering option
2 : communication option
/
Reserved manufacturer
1
Option slot 1
0xFF : no option
0x0 : metering option
0x1 : communication option
1
Option slot 2
0xFF : no option
0x0 : metering option
0x1 : communication option
Example : metering + communication will correspond
at number 3, that's to say 1 + 2.
No. of words
Text
1
Network type :
0 : 1BL
1 : 2BL
2 : 3BL
3 : 3NBL
4 : 4BL
5 : 4NBL
1
CT secondary:
5 : 5A
1
CT primary
Reserved manufacturer
1
Synchronisation of I MAX :
2 : 2 sec
5 : 5 minutes
8 : 8 minutes
10 : 10 minutes
15 : 15 minutes
20 : 20 minutes
30 : 30 minutes
60 : 60 minutes
1
Synchronisation of P MAX :
2 : 2 sec
5 : 5 minutes
8 : 8 minutes
10 : 10 minutes
15 : 15 minutes
20 : 20 minutes
30 : 30 minutes
60 : 60 minutes
1
OUT allocation:
0 : kWh +
1 : kvarh +
DIRIS A20 - RS485 - JBUS/MODBUS
COMMuNICatION
Unit
/
/
/
Unit
/
A
A
/
/
/
DIRIS A20 - Réf. : 536 085 C
®
GB
45