Technical Data - Protector AS-5030.3 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Thermo-sensor (10) of the furnace transmitter
is > 38°C
1. Switch ON exhaust and window is closed
>
Exhaust unit must not start up.
2. Open window
> Exhaust unit must start up.
3. Close window
> Exhaust unit must switch off.
MEANING OF THE LED DISPLAYS
RECEIVER/CONTROL CENTRE
LED Network (3)
Yellow continuously lit
> Basic position
Yellow flashing at the start > No transmitter taught in
Yellow flashing Teach-in mode > Transmitters can
be taught in
LED Window (4)
Dark
> No transmitter taught in
Green continuously lit
> Window is open
Red continuously lit
> Window is closed
RED and GREEN continuously lit > Window transmitter no
longer has radio reception
(Battery discharged,
defective or no radio
reception)
LED Furnace (5)
Dark
> No transmitter taught in
Green continuously lit
> Furnace is cold
Red continuously lit
> Furnace is hot
RED and GREEN continuously lit > Furnace transmitter no
longer has radio reception
(Battery discharged,
defective or no radio
reception)
WINDOW TRANSMITTER
Dark
Green flashing
Red flashing
RED and GREEN flashing 0.5 s > Window transmitter
FURNACE TRANSMITTER
Dark
Green flashing
Red flashing
RED and GREEN flashing 0.5 s > FURNACE transmitter
MALFUNCTIONS
Malfunctions can occur in individual cases due to overlaps
with other, similar radio devices. It is normally sufficient if
you check and, if necessary, adjust the positioning of the
components. If one of the transmitters is no longer reachable
(battery discharged, mechanically defective or no radio
reception), the control centre no longer interconnects as long
as the fault is present.

TECHNICAL DATA

Mains voltage:
Mains switching capacity: 1800 W / 8A, at cos phi = 1
Radio range up to:
Frequency:
Protection class:
19
ENGLISH | AS-5030
> Rest state / Sleep mode
> Window is being opened
> Window is being closed
battery is discharged
> Rest state / Sleep mode
> FURNACE becoming cold
> FURNACE becoming hot
battery discharged
230 V ~ , 50/60 Hz,
approx. 1 W
50 m
433.92 Mhz
IP 20 * only for dry rooms