Télécharger Imprimer la page

Ace 1-2 2W Manuel D'installation page 3

Masquer les pouces Voir aussi pour ACE 1-2 2W:

Publicité

Les langues disponibles

Les langues disponibles

TABLE 3: Copper Cable Length in Feet (Service to Motor)
R-Series Motors: 1 Ph, 3-Wire Cable, 60 Hz. Wire Size
HP
Volt
14
0.5
230
348
0.75
230
264
1
230
226
1.5
230
197
R-Series Motors: 1 Ph, 2-Wire Cable, 60 Hz. Wire Size
HP
Volt
14
0.5
230
466
0.75
230
342
1
230
241
NOTE:
1. Maximum wire lengths shown maintain motor voltage at 95% of
service entrance voltage, running at maximum nameplate
amperes. If service entrance voltage will be at least motor name-
plate voltage under normal load conditions, 50% additional length
is permissable for all sizes.
2. Sizes given are for copper wire. For aluminum wire go two sizes
larger (i.e., if table lists #12 (3mm
aluminum wire.)
INSTALLATION WIRING INSTRUCTIONS
Single Phase, 3 Wire
Hazardous voltage. Can shock, burn, or kill.
Ground control box, all metal plumbing, and motor frame with copper
wire in compliance with Canadian Electrical Code or National Electrical
Code and local codes. Use ground wire at least as large as the wires
supplying power to motor.
At well head, connect ground wire to grounding terminal that meets
Canadian Electrical Code or National Electrical Code requirements that
apply. For more information, contact local code officials.
Permanently close all unused openings in this and other equipment.
Disconnect power before working on or around control box, pipes, cable,
pump, or motor.
NOTICE: Install control box vertically on wall with top side up.
3-Wire pumps have three power supply wires (Red/Black/Yellow) and
one ground wire (Green).
Attempting to operate 3 wire pump without a control box will burn out the
motor.
Installations must include circuit and component protection in compli-
ance with U.S. National Electrical Code or Canadian Electrical Code,
Part 1.
If main overload trips, look for:
1. Shorted Capacitor
2. Voltage Problems
3. Overload or locked pump.
NOTICE: Use only control box specified for your pump. Make sure
motor and control box match (Table 4). FAILURE TO DO SO WILL
VOID WARRANTY.
Table 4: Control Box Chart
HP
Voltage
Control Box No.
1/2
230
3/4
230
1
230
1-1/2
230
For motors of 1-1/2 HP and above, use magnetic
starter to avoid damage to pressure switch. Consult factory for
wiring information.
Wire Size, AWG
12
10
8
6
553
883
1398
2175
420
670
1061
1651
359
573
908
1413
314
501
793
1234
Wire Size, AWG
12
10
8
6
742
1183
1874
2915
545
869
1376
2141
383
611
968
1506
) copper wire, use #10 (5mm
2
SD-F303
SD-F304
SD-F305
SD-F306
4
3
2
3467
4359
5505
6935
2632
3309
4178
5264
2252
2831
3575
4504
1968
2474
3124
3936
4
3
2
4648
5843
7379
9295
3413
4291
5419
6826
2400
3018
3811
4801
Fig. 1A – 3 wire - 1/2 thru 1 HP quick disconnect box.
115V or
Ground
230V Line
Fused
disconnect
switch
)
2
L1 M1
L2
M2
Red
Yellow
Black
Well
casing
Single Phase, 2 Wire
2-Wire pumps have two power supply wires (Red/Black) and one
ground wire (Green). Control box is not required.
See Figure 1B for correct hook-up information for 230 Volt 2-Wire
motors only.
To Line
Ground
L1
M1
L2
M2
Fused
Disconnect
Switch
Pressure
Switch
Red
Black
Well
Casing
Fig. 1B – Single phase, 2 Wire Connections
Follow color coding when connecting control box.
(Yellow to Y, Red to R, Black to B)
3
1
0
00
8753
11044
6644
8383
5685
7173
4968
6268
1
0
00
11733
14803
8617
10871
6060
7646
Sub.
Motor
Control
L1L2R Y B
Pressure
switch
Ground
699 0993
Ground
(Green)
336 1093

Publicité

loading

Produits Connexes pour Ace ACE 1-2 2W