THERMASGARD
READOUT IN THE DISPLAY
A static display of dew point, setpoint potentiometer, relative humidity, and temperature can be preset via MODBUS.
In the first line of the display the measured value and in the second line the corresponding unit is displayed.
The index indicates the display type, e.g. dew-point temperature (see the table "Function 06 Write Single Register").
The Modbus interface allows the display to be individually configured in the 7-segment area and in the dot-matrix area.
For the individual display, the register 4x0001 (physical value displayed) must contain the value 10.
The registers 4x0002 to 4x0012 contain information about the characters and segments to be displayed.
The dot-matrix area is also programmable in the default setting (register 4x0001 contains the value 0).
In this case, the current measured value is automatically displayed in the 7-segment area
Composition of Segment Pattern (Register 4x0005)
Bit 6 ...... - -
Bit 7 ...... - -
Bit 9 ...... - -
Bit 10 .... - -
Bit 11 .... - -
Bit 12 .... - -
Bit 13 .... - -
Bit 14 .... - -
Composition of 14-Segment Pattern (Register 4x0003 And 4x0004)
Bit 0 ...... A
Bit 1 ...... B
Bit 2 ...... C
Bit 3 ...... D
Bit 4 ...... E
Bit 5 ...... F
Bit 6 ...... G
Bit 7 ...... G'
Bit 8 ...... H
Bit 9 ...... I
Bit 10 .... J
Bit 11 .... K
Bit 12 .... L
Bit 13 .... M
Bit 14 .... - -
Bit 15 .... - -
RTM 1- Modbus | Configuration
In the first line of the display, the ACTUAL temperature is displayed.
Resolution: 1/10 °C.
Reading:
13.8
Index:
1
Unit:
°C
Dot A
Dot B
Dot Matrix
A
H
A
F
G
E
M
D
Dot DP
Dot C
B
C
D
E
Example for characters
I
J
Degrees Celsius (°C)
B
G'
C
14-Segment 1:
227
L
K
(Register 4x003)
12
Dot D
Percent
14-Segment 1
F
G
14-Segment 2:
57
(Register 4x004)