ADEUNIS TEMP V4 IP68 LoRaWAN 863-870 Guide Utilisateur page 46

Sonde de température
Masquer les pouces Voir aussi pour TEMP V4 IP68 LoRaWAN 863-870:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

TEMP V4 IP68 LoRaWAN 863-870 - Guide utilisateur / User guide version V3.1.1
functioning of the battery.
2.2. JOIN process
2.2.1 Start-up of the product, JOIN process and configuration
The product start the JOIN process after entering PRODUCTION mode (after the detection of the magnet or after the exit of the command
mode).
FR
By default, the device make 10 successive trials, in case of failure the device waits for 12 hours and then restarts the process. This process will
be repeated until the device receive an accept from the gateway called Join Accept.
It is possible to configure the JOIN process through the IoT Configurator.
With the App you can decide :
How many trials you want for each authentication attempt,
The delay maximum between 2 attempts,
The weighting factor, used to reduce the delay for the first attempts.
EN
Registers concerned by the configuration:
S312: Maximum delay between 2 authentication attempts
S313: Weighting factor for initial authentication attempts
S314: Number of tries for each authentication attempt
Example:
Register Encoding
S312
0x2A30
S313
0x04
S314
0x0F
2.2.2 Launch a JOIN process remotely
The product receives a 0x48 downlink frame and restart after a defined delay (indicated in the frame).
This function of restart enables the device to start a JOIN process remotely. It can be useful for a change of operator or when you have to restart
a gateway.
To know the content of the 0x48 frame refers to the Technical Reference Manual (TRM) of the product.
2.3. Network quality test
During the JOIN Process, a device configured in Class A OTAA will make a network quality test (patented algorithm). When the test is running
the device shows the 2 LEDs green and red simultaneously (from 10 to 20 seconds).
The result of the test is given by the devices after around 20 seconds following the Join Accept. It is visible through the sole thanks to the LED.
With this information the installer know the quality of the network and can move the product to a place with a better coverage.
Value
Result
10800
The maximum delay between each attempts is 4 hours.
The weighting factor indicated that the first attempt will be
4
spaced by 1 hour, then it will increase after each attempt
until it reaches the maximum delay specified in S312.
15
Each attempt is composed by 15 successive trials
Great quality
Medium quality
SF7 or SF8
Other SF and
link margin > 6
Poor quality
Other SF and
link margin <= 6