2
Safety instructions
The D22 517 plugs and sockets
are not suitable for Zones 0, 1, 2
and Zones 20, 21 hazardous
areas.
The temperature class and explosion
group marked on the apparatus shall be
observed.
The electrical connection of the device may
only be carried out by skilled staff.
Modifications to the plugs and sockets or
changes of their design are not permitted.
They shall be used for their intended purpose
and in perfect and clean condition.
The requirements of the EN 61241-0 and -1
regarding excessive dust deposits and
temperature to be considered from the
user.
To ensure adherence to the temperature
class stated on the type label of the
apparatus, the permissible ambient
temperature, the rated terminal cross
section and the self heating of the
apparatus that is mainly due to the power
dissipation shall be taken into account (test
criterion for the self heating is an overload
of 10%).
For replacement and repair only genuine
COOPER CROUSE-HINDS spare parts shall
be used.
Repairs that affect the explosion protection,
may only be carried out by COOPER
CROUSE-HINDS or a qualified electrician in
compliance with the respective national
regulations.
Prior to taking the plugs and sockets into
operation, they will have to be checked in
accordance with the instruction as per section 6.
The interlocking switch of the socket is
mechanically secured and cannot be
connected without plug.
The sockets may only be used with the
associated COOPER CROUSE-HINDS
plugs in undamaged condition.
The plugs D22 532 can further on be
inserted with the sockets of the series
D22 532.
Before the initial operation, any foreign
matter will have to be removed from the the
plugs and sockets.
Flange sockets may only be used in
protective enclosure or apparatus that have
been certified for the respective application.
Observe the national safety rules and
regulations for prevention of accidents as
well as the safety instructions included in
these operating instructions and set in
italics the same as this text!
6 6 6 6 6
Cooper Crouse-Hinds GmbH
Explosion protected plug and socket system 32A,
1

Technical data

Marking acc. to 94/9/EC:
EC type examination certificate:
Wall socket
Plug
Coupler
Flange socket
Plug
Plug
Rated voltage:
D22 517
Plug D22 532 7.
Rated current:
Back-up fuse:
without thermal protection
with thermal protection
Switching capacity AC 3:
Perm. ambient temperature:
Special versions permit deviating temperatures.
Perm. storage temperature in original packing:
Protection category acc. to EN/IEC 60529
with closed and secured hinged cover as well
as combinations properly plugged together
* Attention! When the Plugs D22 532 is
insert with sockets of the series D22 517,
the "IP" protection category of the combina-
tion is reduced to the minimum protection
category "IP 54".
Insulation class acc. to EN/IEC 61140:
Cable entry: (catalogue version)
Wall socket
Plug / Coupler D22 517
Plug D22 532
Plug D22 532
Supply terminal:
Wall socket, flange socket
Coupler D22 517
Plug D22 517
Plug D22 532
Test torques:
Cap nut of the entry
for min. cable Ø in Nm
for max. cable Ø in Nm
Cover screws
Terminals
Self-cutting screws size 4
Self-cutting screws size 5
Weight: (catalogue version)
Wall socket
Plug
Coupler
Flange socket
Wall socket
Plug
Coupler
Flange socket
Auxiliary contact, rated voltage:
Auxiliary contact, rated current:
*
1 for preparation
D22 517
D22 517 4.
D22 517 7.
D22 517 3.
D22 517 8.
D22 532.7.
GHG 531 7.
2 x M40
3-pole+PE
4-pole+PE
4-pole
D22 517 44
4-pole
D22 517 74
4-pole
D22 517 34
4-pole
D22 517 84
5-pole
D22 517 45
5-pole
D22 517 75
5-pole
D22 517 35
5-pole
D22 517 85
II 3 D Ex tD A22 IP 66 T 80°C*
BVS 07 ATEX E 116
BVS 07 ATEX E 116
1 In Vorbereitung
BVS 07 ATEX E 116 *
BVS 07 ATEX E 127 U
BVS 07 ATEX E 116
BVS 07 ATEX E 116
up to 690V, 50/60Hz
up to 690V, 50/60Hz
max. 32 A
D22 517
D22 532
max. 35 A
35 A
max. 50A gL
40 A gL
690 V/32 A
-20° C to +40° C (catalogue version)
-40° C to +80° C
IP 66 (catalogue version) *
I - is complied with by the devices
1x
Ø 17 - 28mm + 1x screwed blanking plug
Ø 12 - 28 mm
Ø 13 - 20 mm
Ø 18 - 27 mm
Cross section
Stripped wire length
2 x 4.0 - 10 mm²
2 x 4.0 - 10 mm²
1 x 1.0 - 6.0 mm²
1 x 1.0 - 6.0 mm²
M20
M25
M32
M40
3.50
5.00
8.00
11.0
2.50
3.50
5.00
5.0
2.5 Nm
2.5 Nm
2.0 Nm
3.0 Nm
approx. 2.25 kg
approx. 0.55kg
/ D22 532 - approx. 1.10kg
approx. 1.50 kg
approx. 1.00 kg
approx. 2.30 kg
approx. 0.60kg
/ D22 532 - approx. 1.15kg
approx. 1.60 kg
approx. 1.05 kg
250 VAC
AC / 5 A
DC / 0.03 A
12 mm