2. Troubleshooting
Flash sequence table
LED

Solid green
Red off
   
Green blinking
slow
Red off
Green off
Red off
Green off
− − − − − − − −
Red blinking
fast

Solid green

Solid red
Green off

Solid red

Solid green
   
Red blinking
slow
Green off
   
Red blinking
slow

Solid green
− −
Red blinking
intermittently
Green off
− −
Red blinking
intermittently
Normal operation
Search mode active
Inverter off
Over voltage
Imminent shut down due to
overload
Overload
Imminent shut down due to
under voltage
Under voltage
Imminent shut down due to
− −
− −
over temperature
Over temperature
− −
− −
Status
If a load is connected, and the
inverter does keep switching on
and off, the load may be too small:
increase load.
Check the switch on the inverter:
should be in on position or in
search mode position.
Check remote switch connection.
Check DC cable connections.
Inverter fuse blown: the inverter
has to be returned for service.
Reduce DC input voltage.
Reduce load.
Reduce load.
Switch the Inverter off, wait 2
seconds and switch the Inverter
on.
Recharge or replace battery.
Check DC cable connections.
In case of long DC cables: cable
cross section may be insufficient.
Recharge or replace battery.
See Technical Data for restart
voltage.
Reduce load.
Wait for the inverter to cool down
and reduce load.
Solution
3