Only guide antenna cable individually
i
through the cable feedthrough. Feed-
throughs not needed must remain
sealed.
7. Attach antenna cable to antenna bush "A"
and screw down by hand.
8. Position antenna (magnet) on ventilation
unit or at suitable location.
9. Slide the electronic slide-in module into the
electronic compartment and screw down if
necessary (depending on unit type).
10. Fit front cover(s) Installation instructions
for ventilation unit.
11. Affix the retrofit sticker provided on the
ventilation unit such that it is clearly visible
and enter installed function E-SM.
12. Switch the mains fuse on. Switch on the
ventilation unit.
13. Use the commissioning software, comfort
control unit (installer level) or web server
to set the EnOcean wireless parameter
to yes.
14. Set the Learning mode parameter to ac-
tive. "Learning mode active" appears.
15. Press the learn button on the EnOcean
component. The learn telegram is sent to
the unit control. The component ID and
EEP protocol number (A5-04-01, A5-09-
08, A5-09-04) appear on the screen.
For the EnOcean 4-channel wall
i
transmitter (company PEHA) the
EEP protocol number (F6-02-01)
has to be entered manually.
i
Learning tips
●Currently supported EEP protocols can be found
in the EnOcean EPP list under http://www.
maico-fans.com/search/results/?q=0092.0556
Downloads Product description.
●Up to 8 EnOcean sensors/operator units
can be learnt.
●The learning mode is deactivated each
time an EnOcean component is saved.
●If no components are detected, learning
mode deactivates after 60 seconds.
●Once a component has been learnt, it is
listed in the EnOcean unit editor.
●The Unlearn devices parameter is used to
delete all learnt components. Individual
components are unlearnt via the unit editor.
16. Assign EnOcean component to a particu-
lar room if you want. The learning mode is
deactivated each time an EnOcean com-
ponent is saved. The superordinate menu
item appears. Activate learning mode
again to learn more components.
17. The unit editor in the EnOcean menu can
be used to check that all components are
correctly learnt. More information, such
as unit ID, type, EEP, ok/not ok status,
measurements and the room assignment
can be queried by selecting a unit. Indivi-
dual components can also be unlearnt.
The "not ok" status appears if a com-
i
ponent does not automatically register
within 60 minutes.
18. Test all settings and functions.
For quick access to the EnOcean unit
i
editor, select the EnOcean wireless
parameter under Query.
5 Technical data
Dimensions (WxD)
Rated voltage
Frequency range (in acc. with
EN 300220-1)
Operating distances in the building
are dependant on the building
materials used
.
54 x 39 mm
3.3 VDC
868.3 MHz
up to 30 m