• test signal strength with impulse
tester (optional, Article number
E30082). The result of the impulse
test must be >5 mg / N
• the signal direction is correct
• ensure a safe vibration transmis-
sion and allow no elastic inter-
mediate layers
Operation/LED display
Please ensure that the vibration diagnostic unit is correclty para-
meterized for your application using the Expert Software
(VES001). If there are no parameter sets present all LEDs light up
(delivery status).
Press the TEACH pushbutton for 5s.
The parameterized vibration dia-
gnostic unit automatically adapts to
the existing operating conditions.
The yellow LEDs 2, 3 and 4 then
flash.
When the Teach-In is conducted the
green LED flashes, afterwards the
unit passes into the monitoring
mode. The green LED lights.
When the Teach-In is conducted
using a laptop the green LED flas-
hes. A corresponding message
appears on the screen, the green
LED lights.
The unit is now in the monitoring
mode and indicates progress dama-
ge by LEDs.
M5 screw
washer
spacing ring
machine surface
ok
check
NEXT
measuring axis
react
A
B
L
TEACH
9