Maico TH 16 Notice De Montage page 7

Publicité

Les langues disponibles

Les langues disponibles

7. Function/Operation
When the temperature exceeds/falls below
the setpoint temperature, the thermostat
switches one or more fans on/off.
The setpoint temperature can be set using
the rotary knob [2].
The differential gap between the switch-on
and switch-off temperature is 1.5 K.
8. Technical data
 Rating plate on the unit.
Rated voltage
Power frequency
Maximum loading
(inductive load)
250 V AC, terminal 1-3
250 V AC, terminal 1-2
400 V AC, terminal 1-3
400 V AC, terminal 1-2
Maximum loading
(ohmic load)
250 V AC, terminal 1-3
250 V AC, terminal 1-2
400 V AC, terminal 1-3
400 V AC, terminal 1-2
Maximum switching
current
Differential gap
Degree of protection
Protection class
Type of installation
Weight
Dimensions (WxHxD)
9. Environmental conditions and
operating limits
Ambient temperature:
Temperature setting range
250 V AC /
400 V 3 Ph
50/60 Hz
4 A
4 A
4 A
2 A
16 A
8 A
10 A
4 A
cos ϕ ≥ 0,8
1.5 K
IP 54
I
Surface-
mounted
0.3 kg
115x150x68 mm
max. + 50° C
0 to +50 °C
7. Function/Operation │ UK
10. Storage
Store unit exclusively in a dry location (-20 to
+50 °C).
11. Mounting
11.1 Mounting instructions
NOTICE
Incorrect measured values can result
from unsuitable installation location.
Locate the temperature sensor [7]
correctly.
 Avoid disturbing influences.
 Avoid exposure to direct sunlight.
 Do not use in an area prone to draughts,
hot or cold air, e.g. near stove, fridge,
radiator, refrigerator, air intake, disk
valve/internal grille, etc..
 Do not install in a unit with other heat-
generating devices, e.g. a dimmer switch.
● Only install unit onto a dry, level surface.
Any installation position can be selected.
● Only connect the unit to a permanently
wired electrical installation after it has
been completely mounted.
● The unit may only be operated using the
voltage and frequency shown on the rating
plate.
● Be sure to observe the relevant regula-
tions for electrical installation; in Germany
this is particularly VDE 0100, with the
corresponding parts.
● Connection area for the PG screw connec-
tion [3] is suitable for connection cables
with an external diameter of 6 to 12 mm.
● Connection terminals for cable with a max.
cross section of 2.5 mm².
● A mains isolation device with contact
openings of at least 3 mm at each pole is
mandatory.
● The degree of protection is only
guaranteed if installation is undertaken
correctly and if the cables are correctly fed
into the housing.