Malfunction
Communication
between controller and main
board
Communication
between Main control board
and Driving board
VDC voltage too high protection
IPM module protection
VDC voltage too low protection
Input
current
over
protection.
IPM module thermal circuit is
abnormal
Error code
failure
1. Poor signal wire connection or
EE08
damaged signal wire
2. Controller malfunction
failure
1. Poor
EE09
communication wire
2. The wire is damaged
1. Line voltage is too high
EE10
2. Driver board is damaged.
1. Data mistake
2. Wrong
connection
3. Compressor
EE11
accumulation lead to the current
becomes larger
4. Compressor or driver board
damaged
1. Mother line voltage is too low
EE12
2. Driver board is damaged.
1. The compressor current is too
large momentary
2. The water flow is abnormal
high
3. Power fluctuations within a
EE13
short time
4. Wrong PFC inductor
1. Output
module thermal circuit
2. Fan motor is abnormal or
EE14
damaged
Fan blade is broken
Reason
connection
compressor
phase
liquid
and
oil
abnormity
of
IPM
38
Solution
1. Check and re-connect the
signal wire
2. Change a new signal wire
3. Turn off electricity supply
and restart machine
4. Change controller
of
1. Check the wire connection
2. Change wire
1. Check if the power is in the
normal range
2. Change driver board or main
board
1. Program error, turn off
electricity supply and restart
after 3 minutes
2. Change driver board
3. Check compressor sequence
connection
1. Check if the power is in the
normal range
2. Change driver board
1. Check the compressor
2. Check the waterway system
3. Check if the power is in the
normal range
4. Check if the correct PFC
inductor is used
1. Change a driver board
2. Check if the motor speed is
too
low
or
fan
damaged, change it.
3. Change fan blade
motor