Bering BEXP05i Manuel D'installation Et D'utilisation page 27

Pompe à chaleur pour piscine
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 65
NOTE:
(1) Above electrical wiring diagram only for your reference, please subject machine posted the wiring diagram.
(2) The swimming pool heat pump must be connected ground wire well, although the unit heat exchanger is
electrically isolated from the rest of the unit. Grounding the unit is still required to protect you against short circuits
inside the unit. Bonding is also required.
Disconnect: A disconnect means (circuit breaker, fused or un-fused switch) should be located within sight of and
readily accessible from the unit. This is common practice on commercial and residential heat pumps. It prevents
remotely-energizing unattended equipment and permits turning off power at the unit while the unit is being
serviced.
6.2 Electrical protection
The power supply for the heat pump must come, preferably, from an exclusive circuit with regulatory protection
components (30mA differential protection) and a magneto-thermal switch.
- The electrical installation must be carried out by a specialized professional (electrician) in accordance with the
standards and regulations in force in the country of installation.
- The heat pump circuit must be connected to a safety earth circuit at the terminal block.
- The cables must be properly installed to prevent interference.
- The pump is intended for connection to a general power supply with earth connection.
- Section of the cable; This section is indicative and should be checked and adapted according to the needs and
conditions of use.
- The tolerance of acceptable voltage variation is +/- 10% during operation.
The connections must be dimensioned according to the power of the device and the state of
installation.
Models
BEXP05i
BEXP07i
BEXP09i
BEXP11i
BEXP14i
BEXP16i
BEXP18i
BEXP20i
BEXP25i
BEXP30i
These values are given as a guideline, only an authorised electrician can determine the values
corresponding to your installation. The electric cable must be equipped with a ground connection and
with a circuit breaker with difference 30mA.
Circuit breaker
2,5 mm²
7A
7A
9A
11A
14A
16A
18A
20A
25A
35A
Maximum length of the wire
4 mm²
84m
135m
84m
135m
57m
90m
57m
90m
43m
68m
34m
54m
32m
50m
29m
45m
/
35m
/
/
23
6 mm²
10 mm²
200m
335m
200m
335m
130m
225m
130m
225m
100m
170m
80m
135m
75m
128m
66m
110m
52m
95m
40m
75m