TECHNICAL SPECIFICATIONS
MODEL
INPUT
OUTPUT
PROTECTION AND
FILTERS
BATTERY
Typical recharge time
PHYSICAL
CHARACTERISTICS
ALARMS
INTERFACE
ENVIRONMENTAL
CONDITIONS (1)
OTHERS
(1) In order to prolong battery life, make sure that the UPS is used/stored at a temperature of 20-25°C and
keep it connected to the mains to preserve the battery charge.
Capacity
Frequency
Maximum Current
Voltage
(on battery)
Frequency
(on battery)
AVR automatically increases the output voltage by 17% if the input voltage drops by -
Voltage Regulator
10%-26% below nominal. AVR decreases the output voltage by 15% if the input
AVR
Transfer time
Nominal power VA
Nominal power W
Current
EMI/RFI Filter
Protection against
Battery: the UPS shuts down after 30 seconds if the load is between 100 ~ 110% of
overloads and short
the nominal, after 5 seconds if it exceeds 110%, or immediately in the event of a
circuits
Type
Model
Protection
Net weight (Kg)
Dimensions(mm)
WxDxH
Input plug
Output plug
Battery Mode
Battery Failure
Overload <110%
Overload >110%
Disable buzzer
RS-232 Interface
RS-232 protocol
Environmental
Conditions
Noise Level
NDG 800
NDG 1000
50 o 60Hz +/-5% (auto sensing)
5 A
6.3 A
Simulated sinus wave 230Vac +/- 5%
50 or 60Hz +/-0.5% (auto sensing)
voltage increases by +9% -+20% above nominal
800
1000
480
600
3.48A
4.35A
10dB at15MHz, 50dB at 30MHz
Mains: thermal protection switch for overloads and short circuits
Lead acid, sealed, maintenance free
2x12V 7Ah
2x12V 7Ah
Protection against battery failure, battery replacement indicator
13,5
13,5
140x370x180
Slow beep (approx. 0.20Hz)
Fast beep (approx. 1Hz)
Fast beep (approx. 1Hz)
Bi-directional communication port
max. altitude: 6,000 metres, 0-90% non condensing humidity
<50dBA (1m from source)
- 36 -
NDG 1500
230Vac -25% / +20%
9.4 A
Typically 6-8 ms
1500
900
6.52A
short circuit.
2x12V 9Ah
6-8 hours
14,7
IEC 320-10A
N°4 x IEC 320-10A
Continuous beep
YES
PSGPSER-0103
0-40°C
NDG 2000
10 A
2000
1200
8.70A
3x12V 9Ah
20,3
140x400x217