Two Hand Control Device EduTrainer
10 Status LEDs
Legend
Symbol
Meaning
LED illuminated
LED flashing
LED off
Status indicators
Power In1
In2
Fault displays
Power In1
In2
38
®
Out
Reset Fault
Meaning
Supply voltage present
Pushbutton on S13 is actuated
Pushbutton on S23 is actuated
Safety contacts are closed, semiconductor output Y32 on high signal
24 V DC present on S34
Out
Reset Fault
Meaning
Supply voltage not present, cross circuit or ground fault present
Internal fault, device defective, (switch the supply voltage on and off again, if necessary)
Supply voltage too low
Connection error detected in the input circuit or cross circuit between S14 and S24
Simultaneity limit exceeded: Channel 1 too late or switch-on blocked due to short
interruption on S13; Input circuits not actuated at the same time
Simultaneity limit exceeded: Channel 2 too late or switch-on blocked due to short
interruption on S23; Input circuits not actuated at the same time