3-wire pnp sensor
L+
L
A
Bulb
L+
A
Addressing
Assign a free address between 1 and 31. At the factory the address
is set to 0.
A Addressing with the addressing unit
Connect the addressing unit with the terminals A+ and A-, remove
the addressing plug and assign the desired address.
B Automatic addressing with the ifm AS-i controller
All present slaves must be projected.
Connect the module with the controller (function MULTIPLE AUTO
ADDRESS = ON). Remove the addressing plug. The lowest available
address is used.
Automatic addressing of several modules: Remove the addressing
plug of the first module, continue with the addressing plug of the
second module etc. The modules are addressed in rising order.
C Addressing via AS-i software
Connect the module and assign the desired address.
Caution! If you address several modules, only one module with the
address 0 may be present on the AS-i network, and so all addressing
plugs must first be inserted.
8
Mechanical
switch
I+
I-
I1
2-wire solenoid
(free wheeling diode recommended)
O1
O-
(E-)
2-wire sensor
L+
I+
A
I1
+
O1
-
O-
(E-)
L+
I+
A
I1