The pressure sensor ⁄ differential pressure sensor PREMASGARD
converts the measurand into standard signals of 0-10 V or 4...20 mA. Process connection is 2 x G ⅛ " - 27 NPT internal thread. SHD -692 differential
pressure transmitters are used in piping and hydraulic systems, in mechanical and plant engineering as well as in building automation.
Not applicable for ammonia and Freon!
TECHNICAL DATA
Power supply:
Measuring ranges:
Output:
Permissible working resistance:
(at nominal voltage)
Electrical connection:
Pressure connection:
Type of pressure:
Measuring principle:
Medium:
Temperature of medium:
Mounting:
Housing:
Medium contacting parts:
Response time:
Class:
Total error:
Overload range:
System pressure:
Bursting pressure:
Insulating resistance:
Protection class:
Protection type:
Standards:
ACCESSORIES:
PREMASGARD
®
SHD 692
Type ⁄ WG02
SHD 692 - U
S H D 6 9 2 - U - 9 0 0
S H D 6 9 2 - U - 9 0 7
S H D 6 9 2 - U - 912
S H D 6 9 2 - U - 916
S H D 6 9 2 - U - 918
SHD 692 - I
S H D 6 9 2 - I - 9 0 0
S H D 6 9 2 - I - 9 0 7
S H D 6 9 2 - I - 912
S H D 6 9 2 - I - 916
S H D 6 9 2 - I - 918
Note:
ACCESSORIES
LCD - SHD
SHD 692
24 V AC (+15 % / –10 %), 18 - 33 V DC for U-variant
24 V DC (± 20 %) for I-variant
see table
0 -10 V (3-wire connection) or
4...20 mA (2-wire connection)
R
> 10 kΩ
for U-variant
L
R
< 600 Ω
for I-variant
L
0.25 - 1.5 mm²,
via plug-in connector DIN EN 175301-803-A
(included in the scope of delivery)
screw pipe connection for 6 mm pipe
(G ⅛ " - 27 NPT internal thread)
differential pressure
ceramic measuring cell
liquid or gaseous
–15...+80 °C
by mounting angle (included in the scope of delivery),
installation arbitrary
stainless steel V2A (1.4305)
INOX (1.4305), ceramics, sealing material EPDM
< 5 ms
0.5 %
< 1.3 %
see table (one-sided max. pressure)
max. 25 bar (P1 + P2)
1.5 x system pressure
≥ 100 MOhm, at +20 °C (500 V DC)
III (according to EN 60 730)
IP 65 (according to EN 60 529)
CE conformity, electromagnetic compatibility
according to EN 61 326, EMC directive 2014 ⁄ 30 ⁄ EU
Display-Modul, made of plastic, polyamide material,
black colour, extra height: approx. 73 mm, pluggable,
factory-calibrated and configured,
for displaying the differential pressure (in bar, other units available upon request)
Pressure measuring transducers, Deluxe
or gaseous and liquid media
Measuring Range
One-Sideed
max. pressure
0...0,1 bar
0,6 bar
0...0,5 bar
0... 1 bar
0...2,5 bar
12 bar
0... 4 bar
12 bar
0...0,1 bar
0,6 bar
0...0,5 bar
0... 1 bar
0...2,5 bar
12 bar
0... 4 bar
12 bar
Not applicable for ammonia and freon !
Display-Modul, factory-calibrated and configured, pluggable,
LCD display rotatable and tiltable (in bar, other units available upon request)
®
SHD-692 is used for pressure measurement in gaseous and liquid media. It
Output
0 -10 V
3 bar
0 -10 V
5 bar
0 -10 V
0 -10 V
0 -10 V
4...20 mA
3 bar
4...20 mA
5 bar
4...20 mA
4...20 mA
4...20 mA
Rev. 2021 - V15
Item No.
U - variant
1301- 4121- 0500-000
1301- 4121- 0510-000
1301- 4121- 0520-0 00
1301- 4121- 0530-0 00
1301- 4121- 0540-0 00
I - variant
1301- 4122- 0500-000
1301- 4122- 0510-000
1301- 4122- 0520-0 00
1301- 4122- 0530-0 00
1301- 4122- 0540-0 00
Extra charge