Electronic frost protection thermostat ⁄ frost monitor THERMASREG
copper, additional control input 0 -10 V and summation output 0 -10 V, optional with or without display. The frost sensor is used for monitoring air
conditioning systems, heat exchangers, heating registers and similar equipment preventing frost damage and freezing up. The sensor can detect when
the temperature falls below the limit value at the coldest measuring point of the capillary tube. In case of capillary breakage, power failure, or electrical
damage at the device, the frost protection monitor's relay automatically switches to frost. Mounting clamps MK-05-K are included in the delivery.
TECHNICAL DATA
Power supply:
Load resistance:
Measuring range:
Output:
Current consumption:
Accuracy:
Hysteresis of switching step:
Switch-on ⁄ start-up time:
Response time:
Sensor and capillary:
Temperature:
(Sensor and capillary)
Ambient temperatures:
Ambient temperature (Enclosure):
Enclosure:
Enclosure dimensions:
Cable gland:
Process connection:
Electrical connection:
Humidity:
Protection class:
Protection type:
Standards:
®
THERMASREG
FS – Two-phase frost protection thermostats
Type ⁄ WG02
Measuring Range
FS
F S1- U
0...+15 °C
F S 2 - U
0...+15 °C
FS x x HE
F S1- U H E
0...+15 °C
F S 2 - U H E
0...+15 °C
Accessories
KRD-04
Capillary tube gland bracket
MK-05-K
Mounting clamps (6 pieces) plastic (included in the scope of delivery)
WS-03
Sunshade and weather protection, 200 x 180 x 150 mm, stainless steel
Function
Relay output
"Frostprotection"
W
Ö
S
Switchpoint "FS"
Adjustable 0-15°C
Ö
(NC)
W
Normally
closed
FS
24 V AC ⁄ DC
R
> 50 kOhm
L
0...+15 °C
1 x 0 -10 V (equivalent to 0...+15 °C)
1 x 0 -10 V summation output (frost signal and control voltage)
1 x potential-free changeover contact (24 V), setting range 0...+15 °C
max. 10 mA at 24 V DC
± 1 K (at +10 °C)
2 K
< 1 min
t
< 5 s
90
copper, active over the entire sensor length, min. 25 cm
–20...+60 °C
(capillary tube at a distance > 20 cm away from enclosure)
maximum operating temperature: +70 °C (+158 °F)
minimum operating temperature: w + min. +2 °C (min. +3.6 °F)
storage ⁄ transport: –30...+70 °C (–22...+158 °F)
–15...+50 °C
plastic, UV-stabilised, material polyamide, 30 % glass-globe reinforced, with quick-locking screws (slotted ⁄
Phillips head combination), colour traffic white (similar to RAL 9016), enclosure cover is transparent!
126 x 90 x 50 mm (Tyr 2)
M 16 x 1.5; including strain relief, exchangeable, max. inner diameter 10.4 mm
by mounting clamps MK- 05 - K (included in the scope of delivery)
0.14 - 1.5 mm² via terminal screws
< 95 % r. H., non-precipitating air
III (according to EN 60 730)
IP 65 (according to EN 60 529)
CE conformity, electromagnetic compatibility according to EN 61 326, EMC directive 2014 ⁄ 30 ⁄ EU
Output
2 x 0 -10 V, 1 x changeover contact
2 x 0 -10 V, 1 x changeover contact
2 x 0 -10 V, 1 x changeover contact
2 x 0 -10 V, 1 x changeover contact
W
Ö
S
Temperature
Switchpoint "FS" +2K
Unlock / reset
automatically or manually
(COM)
S
(NO)
Common –
Normally
Changeover
open
®
FS with continuous and switching output, fully active sensor rod made of
Sensor Length
3.0 m
6.0 m
3.0 m
6.0 m
Temperature output "Temp."
Output voltage
Temperature "Temp."
10V
0V
0°C
Temperature
15°C
"FS-U"
Item No.
1102- 1012- 0102- 020
1102- 1011-0102- 020
with heating element
1102- 1012- 0112- 020
1102- 1011-0112- 020
7 100-0030- 7000- 000
7 100-0034- 1000- 000
7100-004 0-6000- 000
Output "AV"
Output voltage "AV"
at STE = 0V
10V
Displacement
through ST-E
"AV" max. 10V
0V
"FS"
"FS" +6K
Temperature difference
Rev. 2018 - V30 GB