Hubbell EFP Directives D'installation page 9

Table des Matières

Publicité

FD4e v5.02
(1)
101 SYSTEM SETPOINTS
Engine Start
Pressure
[100.0]psi
0-999.9
(1)
102 SYSTEM SETPOINTS
Engine Stop
Pressure
[110.0]psi
0-999.9
(1)
103 SYSTEM SETPOINTS
Engine Start Delay
Time
[ 1] seconds
1-999
(2)
104 SYSTEM SETPOINTS
Engine Automatic
Stop Enabled
[Yes]
(1)
105 SYSTEM SETPOINTS
Engine Minimum
Run Time
[30]minutes
30-99
(2)
106 SYSTEM SETPOINTS
Automatic Weekly
Engine Test Run
[No]
(1)
107 SYSTEM SETPOINTS
Auto Weekly Engine
Test Day Of The Week
[Mon]
(1)
108 SYSTEM SETPOINTS
Auto Weekly Engine
Test Start Time
[10:00:00]
(1)
109 SYSTEM SETPOINTS
Auto Weekly Test
Length Of Run Time
[30] minutes
30-99
(1)
110 SYSTEM SETPOINTS
Auto Weekly Test
Oil/Water Shutdown
[No]
(1)
111 SYSTEM SETPOINTS
Power Failure Engine
Startup
[No]
(1)
112 SYSTEM SETPOINTS
Power Failure Engine
Start Delay Time
[ 1] minutes
0-500
(2)
113 SYSTEM SETPOINTS
Pressure Transducer
Failure Engine Start
[Yes]
(2)
114 SYSTEM SETPOINTS
Fail to start input
MB22 for unavailable
[No ]
(1)
115 SYSTEM SETPOINTS
Shutdown On Low
Intake Contact Type
[NO ]
(2)
116 SYSTEM SETPOINTS
Shutdown On Low
Intake Pressure/Lvl
[No ]
(1)
117 SYSTEM SETPOINTS
Shutdown On Low
Intake Trip Time
[ 20]seconds
0-999
(1)
118 SYSTEM SETPOINTS
Low Intake Shutdown
Auto Reset
[Yes]
(1)
119 SYSTEM SETPOINTS
Low Intake Shutdown
Auto Reset Time
[ 20]seconds
0-999
(1)
120 SYSTEM SETPOINTS
Pressure Switch
Engine Start
[No ]
(1)
121 SYSTEM SETPOINTS
Deluge Valve
Engine Start
[Yes]
(2)
122 SYSTEM SETPOINTS
High System Pressure
Alarm
[175.0]psi
999.9
(2)
123 SYSTEM SETPOINTS
Engine Lockout
Latched
[NO]
(2)
124 SYSTEM SETPOINTS
Remote Start
Input Contact Type
[NO ]
F:\Engineering\Standards\1
Iss 8, 20/01/2016
1
1) SYSTEM SETPOINTS
1) ANALOG SIGNALS
(1)
201 USER PREFERENCES
(2)
303
Set System Real
Time Clock
[17:03:52]
[10]seconds
(1)
(2)
202 USER PREFERENCES
304
Set System Date
[08/10/10]
DD/MM/YY
[10]seconds
(1)
203 USER PREFERENCES
(2)
305
Set System Day
Of The Week
[Sun]
[24]VDC
(1)
(2)
204 USER PREFERENCES
306
Log System Pressure
Battery Low Voltage
Drop Events
[Yes]
[12.0]VDC
(1)
(2)
205 USER PREFERENCES
307
Low Pressure Event
Battery Low Voltage
Trip Pressure
[ 60.0]psi
0-999.9
[ 2]seconds
(1)
206 USER PREFERENCES
(2)
308
Low Pressure Event
Change Tech Password
Reset Time
[******]
[15] seconds
0-20
(1)
(2)
207 USER PREFERENCES
309
Time Between
Pressure Log Samples
[ 15] seconds 15-999
[ 5] minutes
(1)
(2)
211 USER PREFERENCES
310
Enable Remote
System Commissioned
Keypad
[ No]
[31/12/99] DD/MM/YY
(1)
212 USER PREFERENCES
(2)
311
LCD Back Light Mode
DOUBLE SKINNED
FUEL TANK
0=Always on
[No]
[0]]
1=Power Save
(1)
(2)
213 USER PREFERENCES
312
Language Select
ELECTRONIC ENGINE
0=English, 1=Spanish
[Yes]
[0]
(1)
214 USER PREFERENCES
(2)
313
Change User Password
Annunciator Sequence
Level 1
[****]
[STND]
(1)
215 USER PREFERENCES
(2)
314
Save ALL settings
to SD memory card
[No ]
[NO ]
(1)
216 USER PREFERENCES
(-)
316
Load ALL settings
Alarm resound timers
from SD memory card
4Hrs
[No]
24Hrs
(2)
217 USER PREFERENCES
(-)
317
Pressure Units
Alarm Log
Event Log
[bar]
Pr. Log
(1)
218 USER PREFERENCES
(2)
318 TECH SCREENS
Engine Running chrg
Dump Valve
failure alarm
Delay time
[No]
[0]s
(1)
219 USER PREFERENCES
(2)
319 TECH SCREENS
Charger failure
Pressure
delay time
Transducer
[
5]seconds
0-999
[Yes]
(2)
220 USER PREFERENCES
(2)
320
Modbus Address
Weekly Test Start
[
1]
0-255
[NO]
(2)
221 USER PREFERENCES
(2)
321
RS485 com port
Engine Running
Setting
[Device ]
[600]rpm
(2)
222 USER PREFERENCES
(2)
322
Modbus/Printer baud
Engine Overspeed
Alarm
[9600]
[3600]rpm
(2)
223 USER PREFERENCES
(2)
323 TECH SCREENS
Modbus Parity
Pulses Per
Revolution
[None]
[0]
(1)
224 USER PREFERENCES
(2)
324
RESTART
Mode Select
WIFI
0=US, 1=EU
[No]
[1]
(1)= level 2 password
(2)= level 2 password
(-)= no password
D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-French.doc
CONFIG
2) USER PREFERENCES
3) TECH SCREENS
2
CONFIG
2) AUX USER PROGRAMS
TECH SCREENS
(2)
400 ANALOG SIGNALS
Energized To Stop
Analog Input 01
Fuel Solenoid Time
Slope:
0-99
[0.3401360]
(2)
TECH SCREENS
401 ANALOG SIGNALS
Engine Condition
Analog Input 01
Alarm Delay Time
Offset:
[- 76.1904]
1-99
TECH SCREENS
(2)
402 ANALOG SIGNALS
Nominal Battery
Analog Input 1
Voltage
Minimum Counts
10-99
[ 200]
(2)
TECH SCREENS
410 ANALOG SIGNALS
Analog Input 02
Alarm Trip Voltage
Slope:
6-99
[0.0352500]
(2)
TECH SCREENS
411 ANALOG SIGNALS
Analog Input 02
Alarm Trip Time
Offset:
0-99
[
0.0000]
TECH SCREENS
(2)
412 ANALOG SIGNALS
Analog Input 2 1174
Minimum Counts
[
0]
(2)
TECH SCREENS
420 ANALOG SIGNALS
Password Logout
Analog Input 03
Time
Slope:
1-15
[0.0352500]
(2)
TECH SCREENS
421 ANALOG SIGNALS
Analog Input 03
Date
Offset:
[
0.0000]
TECH SCREENS
(2)
422 ANALOG SIGNALS
Analog Input 3 1225
Minimum Counts
[
0]
(-)
ANALOG INPUT COUNTS
TECH SCREENS
649 1176 1221
12
(2)
424 BATTERY 1
TECH SCREENS
Constant A
xA^3 + xB^2 + xC + D
[ 0.0000]
(2)
TECH SCREENS
425 BATTERY 1
Load OID Hardware
Constant B
xA^3 + xB^2 + xC + D
Test Mode
[ 0.0000]
(2)
TECH SCREENS
426 BATTERY 1
Constant C
xA^3 + xB^2 + xC + D
0Min
0Sec
[ 0.00978]
0Min
0Sec
(2)
427 BATTERY 1
TECH SCREENS
Constant D
1/10
xA^3 + xB^2 + xC + D
1/1569
[- 0.05642]
1/25123
(2)
428 BATTERY 1
Volts per count
[1.0000000]
0-999
(2)
429 BATTERY 1
Minimum Amps
[
(2)
430 BATTERY 2
TECH SCREENS
Constant A
xA^3 + xB^2 + xC + D
Due Lamp Only
[ 0.0000]
(2)
431 BATTERY 2
TECH SCREENS
Constant B
xA^3 + xB^2 + xC + D
Speed
[ 0.0000]
200-999
(2)
432 BATTERY 2
TECH SCREENS
Constant C
xA^3 + xB^2 + xC + D
[ 0.00978]
1000-9999
(2)
433 BATTERY 2
Constant D
xA^3 + xB^2 + xC + D
[- 0.05642]
0-999
(2)
434 BATTERY 2
TECH SCREENS
Volts per count
[1.0000000]
(2)
435 BATTERY 2
Minimum Amps
[
Metron Eledyne
24v Defaults
FD4e v5.02
(2)
501
AUX SETPOINTS
Aux User Program # 1
Enabled
[No]
(2)
502
AUX SETPOINTS
Aux User Program # 1
Input Number
[30]
(2)
503
AUX SETPOINTS
651
Aux User Program # 1
Input Contact Type
[NO ]
(2)
504
AUX SETPOINTS
Aux User Program # 1
Trip Time
[
0]sec
(2)
505
AUX SETPOINTS
Aux User Program # 1
Reset Time
[
0]sec
(2)
506
AUX SETPOINTS
Aux User Program # 1
Auto Reset Enabled
[Yes]
(2)
507
AUX SETPOINTS
Aux User Program # 1
Horn Enabled
[No ]
(2)
508
AUX SETPOINTS
Aux User Program # 1
Horn Silence
[No
]
(2)
509
AUX SETPOINTS
Aux User Program # 1
LED Number
[ 0]
(2)
510
AUX SETPOINTS
12
Aux User Program # 1
Output1 Number
[ 0]
(2)
511
AUX SETPOINTS
Aux User Program # 1
Output2 Number
[ 0]
(2)
512
AUX SETPOINTS
Aux User Program # 1
Output3 Number
[ 0]
(2)
513
AUX SETPOINTS
Aux User Program # 1
Record In Event Log
[No ]
(2)
514
AUX SETPOINTS
Aux User Program # 1
Text Message Number
[ 0]
(2)
515
AUX SETPOINTS
Aux User Program # 1
Engine Run Dependent
[
]
(2)
516
AUX SETPOINTS
Aux User Program # 1
Shutdown in Test
0.1]
[
]
(2)
517
AUX SETPOINTS
Aux User Program # 1
Include in First-Up
[
]
0.1]
0-70
0-999
0-999
0-24
0-24
0-24
0-24
0-32
9