5. Dip Switch Details

I SW500 - Input/Output Mode Settings
SW No.
Functions
No. 1
Not in use
No. 2
HA terminal (CN504) input switch
No. 3
HA terminal (CN504) output switch
No. 4
Remote control (CN591) mode switch 1
No. 5
Remote control (CN591) mode switch 2
No. 6
Remote control (CN591) mode switch 3
No. 7
Relay, extermination output mode switch
No. 8
Turn on/off with power option
OFF
ON
Set to OFF
Pulse input
Continuous input
Static mode
Dynamic mode
See the next page
See the next page
On/Off output
Error/Ok output
Turn on/off with
Turn on/off with
power: No
power: Yes
(unit remains off
(Returns the unit to
when the source
the status (on/off) it
power is turned ON)
was in before the
power was turned
off)
Be sure to set these to OFF (When set to OFF, the
unit cannot communicate with the air conditioner).
There is a switch between TC1 and 2 input on the
TB571.
When there is a problem while the unit is running,
it will output a relay ON signal.
When the Auto Restart function on the air condi-
tioner itself is set to ON, be sure to set these to
OFF.
Comments
9