Walls Facing Three Sides; Additional Precautions; Installation Of The Unit; Unpacking The Unit - Daikin Altherma ERLQ018BAVJU Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Walls facing three sides

inch (mm)
>3.94 (100)
>1.97 (50)
>13.78 (350)

6.5. Additional precautions

It is recommended to install the equipment and electric wires keeping
proper distances away from stereo equipment, personal computers,
etc... In extreme circumstances you shall keep distances of 9.84 ft
(3 m) or more and use conduit tubes for power and transmission
lines.
Do not install the unit in places often used as work place.
In case of construction works (e.g. grinding works) where a lot of
dust is created, the unit must be covered.
Do not place any objects or equipment on top of the unit (top
plate).
Do not climb, sit or stand on top of the unit,
Be sure that sufficient precautions are taken, in accordance with
the applicable legislation, in case of refrigerant leakage.
7.
I
NSTALLATION OF THE UNIT

7.1. Unpacking the unit

Check if all unit accessories are enclosed.
WARNING
Tear apart and throw away plastic packaging bags so that
children will not play with them. Children playing with
plastic bags face danger of death by suffocation.

7.2. Inspection

At delivery, the unit must be checked and any damage must be
reported immediately to the carrier's claims agent.

7.3. Handling the unit

As shown in the figure below, bring the unit slowly by grabbing the left
and right grips.
Do not hold the suction inlet in the side of the casing, otherwise the
casing could be deformed.
CAUTION
To avoid injury, do not touch the air inlet or aluminium fins
of the unit.
ERLQ018~030BAVJU
Outdoor unit for air to water heat pump
4PW62590-1 – 07.2010

7.4. Installation instructions

Mounting the outdoor unit

When installing the outdoor unit, please refer to "6. Precautions on
installation location" on page 4 to select an appropriate location.
1
Check the strength and level of the installation ground so that
the unit will not cause any operating vibration or noise after
installation.
2
Prepare 4 sets of 0.31 inch [close to 5/16 inch] (M8) or 0.39 inch
[close to 3/8 inch] (M10) foundation bolts, nuts and washers
each (field supply).
3
Fix the unit securely by means of the foundation bolts in
accordance with the figure below.
It is best to screw in the foundation bolts until their length
remains 0.79 inch (20 mm) above the foundation surface.

Outdoor installation drawing

unit: inch (mm)
6
1
Wrap the insulation pipe with finishing tape from bottom to top.
2
Stop valve cover
3
9.84 inch (250 mm) from wall. Allow space for piping and electrical
servicing.
4
If there is danger of the unit falling or overturning, fix the unit with
foundation bolts, or with wire or other means.
5
Distance from the outer side of the stop valve cover
6
If the location does not have good drainage, place the unit on
block bases. Adjust foot height until the unit is levelled. Failure to
do so may result in water leakage or accumulation.
1
2
3
4
5
Installation manual
6

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Altherma erlq024bavjuAltherma erlq030bavju

Table des Matières