Single Fan Installation For Powerfoil - Bigassfans Powerfoil X2.0 Manuel D'installation

Smartsense
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Single fan installation for Powerfoil X3.0 and
Powerfoil X3.0Plus fans
Variable Frequency Drive
(cover removed)
READY
Analog Common "ACM" (-)
14
ON
ON
RUN
FAULT
1
2
3
1
2
3
RA RB RC
AVI
ACI
NPN
PNP
Analog Current Input "ACI" (+)
WWW.BIGASSSOLUTIONS.COM
Verify that
AVI/ACI is
set to the
DOWN
position for
ACI mode.
Verify that
NPN/PNP
is set to
the UP
position for
NPN mode.
2 conductor shielded cable 18-22 AWG Stranded (provided
by installer) Maximum distance >1000 ft (>305 m)
Top of Wall Pad
SmartSense
Wall Controller
© 2015 DELTA T CORP.
ALL RIGHTS RESERVED.
Upper
Temperature
Sensor
Reserved
Reserved
Reserved
DC Common (shield) (GRAY)
4–20 mA Input from RTS (BLACK)
+24 VDC RTS Supply Out (RED)
4–20 mA Out to VFD (RED)
DC Common (shield) (BLACK)
+24 VDC Supply In (GRAY/WHITE)
DC Common (shield) (GRAY)