Relocation Of The Digital Controller - Daikin EKHBH054BA Manuel D'installation

Unité intérieure pour système de pompe à chaleur air-eau
Masquer les pouces Voir aussi pour EKHBH054BA:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

When connecting the equipment to a benefit kWh rate
power supply, change field setting [D-01]. In case the
benefit kWh rate power supply is of the type that power
supply is not interrupted (like illustrated above as type 1)
change both field settings [D-01] and [D-00]. Refer to
"[D] Benefit kWh rate power supply/Local shift value
weather dependent" on page 33 of chapter "Field settings".
If the benefit kWh rate power supply is of the type that
power supply is not interrupted, the unit will be forced to
off. Controlling the solar pump is still possible.
When the benefit kWh rate signal is sent, the centralised
control indicator e will flash to indicate that the benefit
kWh rate is active.

Relocation of the digital controller

The digital controller is from factory located on the indoor unit. (See
"Main components" on page 10 for actual position). If required, the
digital controller can be repositioned.
Be aware that only 1 digital controller can be connected to the indoor
unit.
Wiring specifications
Wire specification
Type
Section
Maximum length
NOTE
The wiring for connection is not included.
Mounting
NOTE
The digital controller has to be mounted indoors.
1
Remove the front part of the digital controller.
Insert a slotted screwdriver into the slots (1)
in the rear part of the digital controller, and
remove the front part of the digital
controller.
2
Fasten the digital controller on a flat
surface.
Be careful not to distort the shape of the lower part of
NOTE
the digital controller by over tightening the mounting
screws.
EKHBH/X054BA
Indoor unit for air to water heat pump system
4PW54216-1
3
Value
2 wire
AWG18 - AWG16
2
(0.75~1.25 mm
)
1640 ft
(500 m)
4
1
Wire the unit.
6
1
1
2
P2
P1
P2
P1
3
4
5
1
Unit
2
Rear part of the digital controller
3
Front part of the digital controller
4
Wired from the rear
5
Wired from the top
6
Notch the part for the wiring to pass through with nippers, etc.
Connect the terminals on top of the front part of the digital
controller and the terminals inside the unit (P1 to 16, P2 to 16a).
NOTE
When wiring, run the wiring away from the
power supply wiring in order to avoid
receiving electric noise (external noise).
Peel the shield for the part
that has to pass through the
inside of the digital controller
case ( l ).
Reattach the upper part of the digital controller.
CAUTION
Be careful not to pinch the wiring when attaching.
First begin fitting from the clips at the
bottom.
1
Installation manual
21

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ekhbx054baEkhbh030baEkhbx030ba

Table des Matières