CLEANING INSTRUCTIONS
If dust accumulates on the NGC-30-CRM/-CRMS circuit board use
dried compressed air to remove the dust. Turn off all power to the
NGC-30 panel. Carefully disconnect all cables from a single NGC-
30-CRM/-CRMS card, making sure to label cables so that they can
be reconnected after board cleaning. Wear an anti-static wrist
strap connected to ground in order to avoid component damage.
Remove the CRM/CRMS circuit card from the card cage and place
on a clean lint-free surface.
Use dry compressed air from a can for cleaning circuit boards.
(Avoid factory compressed air since it may contain enough
moisture or oil to cause permanent damage.) Use short quick
blasts to remove dust build-up as necessary. After cleaning,
replace the CRM/CRMS in the same card cage position and
reconnect all cables. Remove only one card at a time for cleaning
to avoid any problems during re-installation.
NGC-30-CRM/-CRMS INSTALLATION INSTRUCTIONS
NGC-30-CRM/CRMS
MSB
TB 12
TB 7
1
2
1
Alarm output
2
Relay outputs (5x)
3
LEDs (9x)
4
Fuse
5
12 Vdc Inputs (2x)
6
End of Line (EOL) jumper
7
RS-485 Communications
8
Line & ground-fault sensor
inputs (5x)
9
RTD Inputs
bk
Address Switches
4 | nVent.com
4 | nVent.com
bk
LSB
TB 1
1 2 3
TB 19
TB 6
TB 13
3
4 5 6
7
LED functions
NGC-30-CR INSTALLATION INSTRUCTIONS
Mounting of Card Rack
Use the mounting template (on page 7) to mount the rack on a
panel backplane. There are four holes (0,48 cm dia.) to secure it
to the mounting surface using #8 screws.
Once the card
rack is installed,
a earth bonding
wire must be
connected to the
card rack using
the ground screw
provided.
Note: The card
rack must be
installed on a
non-combustible
surface.
TB 2
TB 3
TB 4
TB 5
TB 14
TB 15
TB 16
TB 17
8
178 mm
(7.00")
279 mm
(10.97")
283 mm
(11.15")
9
273 mm
(10.75")
183 mm
(7.20")
Grounding
screw