ENGLISH
• Connect only to intrinsically safe circuits which are approved with the EC
type test certificate and do not exceed the following maximum values:
• Permissible ambient operating temperature (relating to the maximum
power that can be supplied):
Notes on installation/mounting
• Always observe the applicable national regulations and legal provi-sions.
• Avoid electrostatic charging on plastic units and cables.
• Protect the unit and cables from damage.
• This unit is not suitable for installation in Zone 0/Zone 1 separating walls.
• Always observe the applicable installation regulations.
• Metal parts of the housing must be mounted in such a way that they are
connected to equipotential grounding.
Maintenance/repair
The unit must not be modified in any way and can not be repaired. In the
event of a fault please contact the manufacturer.
If required, the data sheet or the type test certificate may be obtained from
the manufacturer (see cover sheet).
• Maximum effective internal inductance (Li) and capacitance (Ci):
Housing
BES G06MD-GNX10B-EV02-EEX
BES M08MD-GNX10B-EV02-EEX
The values given apply to moulded cables 2 m in length.
I
U
= 15 V,
= 50 mA, P
i
i
see Table 1a/1b
inductance in μH
= 120 mW
i
Totel internal
70
70
GB
IRL
Total internal
capacitance in nF
80
80
7