Installation Steps
1
Installation Kit
Ensure that you have all of the following installation items:
4 Duct Collars
2
Installation Area
The ERV/HRV unit should be installed in a mechanical room or as close to an outside wall as possible.
The ERV/HRV unit must always be installed in an area where the air is conditioned to avoid freezing the
condensate line.
The contractor should install the unit in an area that allows the homeowner easy access for maintenance.
It is very important to install an electric receptacle (120 Vac) near the unit, a separate circuit breaker
is also recommended. It is best to have access to a condensate drain near the ERV/HRV unit to avoid
having to use a condensate pump.
NOTE: Installation is not recommended in unconditioned areas such as an attic or crawl space where
the temperature can fall below 32 ºF (0 ºC).
NOTE: Ducting in unconditioned areas must be fully sealed and insulated.
ERV/HRV Ventilation Systems 69-2480EF—01
Installation Kit:
• 2 Flexible 6 in. Vinyl Ducts
• 1 Condensation Drain Line (10 in.)
• 1 Drain Adapter with Nut
• 4 Tie Wraps (30 in.)
• 16 Hex-head screws (1/4 x 5/8 in.)
• 4 Hex-head screws (1/4 x 1 in.)
• 4 Washers
• 1 Drain cap (VNT5250E100 and VNT5200E1000 only)
• 1 power cord, 120 Vac (not shown)