GPS : description
The GPS version includes BBPR and positioning function.
X
Thanks to
®
(via Bluetooth
A
MART
actuator will reach in case of power failure (BBPR function) as well as setpoint and feedback signal
type (positioning function).
it's also possible to access to actuator parameters in real time, to schedule weekly tasks and to con-
trol it locally.
For any further information, refer to the operation manual (DSBA3304).
The factory default configuration is "normally closed"
Be sure you connect the terminal 15 (-) before the terminal 16 (+)
Following a power failure, the BBPR unit will reset after 4 minutes.
Voltage
Battery capacity
Charging current
Maximum battery charge duration
Charging status feedback relay (65/66)
Failure feedback relay (67/68)
Temperature
TERMINALS

DESCRIPTION

17(-)•18(+)
power supply connector
F(+)•F(-)•T(+)
Battery connector
65•66
Charging feedback connector
67•68
Failure feedback connector
A•0•B
RS485 connector
Positioning setpoint signal
15(-)•16(+)
connector
(0-10 V or 4-20 mA)
Positioning feedback signal
13A(+)•13B(+)•14(-)
connector
13A=0-10 V et 13B=4-20 mA
CV1
Bluetooth
GPS : learning mode

Switch on the actuator

Press both OPEN and CLOSE buttons during 2 seconds. The APPR led confirms that the learning mode is activated.

Press CLOSE button. The valve operate into closed position.

When the valve is closed, press both CLOSE and MEM buttons during 2 seconds.

The APPR2 led blinks rapidly and then lights on. The closed position is stored.

Press OPEN button. The valve operate into open position.

When the valve is open, press both OPEN and MEM buttons during 2 seconds.

The APPR1 led blinks rapidly and then lights on. The closed position is stored

Press both OPEN and CLOSE buttons during 2 seconds. The APPR led lights off. The learning mode is unselected
The both positions open and closed are now stored, so switch into positioning mode.
44
®
connection), it's possible to set the backup position that the
24 V DC
600 mAh
180 mA
3,5 h
24 V DC - 1 A max
24 V DC - 3 A max
-10 °C to +40 °C
®
activation jumper
LED
DESCRIPTION
MANU
manual / Bluetooth
HORO
Weekly scheduler functioning mode
APPR
Learning mode selected
POSI
Positioning mode
Error detected:
 Timestamp memory empty/scheduler selected
 Clock failure
ERROR
 Excessive temperature
 Excessive torque
Power supply:
 Slow blinking (1 s) : charged battery
ACT
 Rapid blinking (0.5 s) : battery charging
APPR1
Open position stored (confirmation)
APPR2
Closed position stored (confirmation)