Par.
Description
7.10
SCHEDULE PROGRAMME 2
7.11
START TIME PROGRAMME 2
7.12
STOP TIME PROGRAMME 2
Par.
Description
8.01
NOMINAL FREQUENCY MOTOR
8.02
UNITS OF PRESSURE
8.03
FULL-SCALE VALUE TRANSDUCER
8.04
MAXIMUM FILTER PRESSURE
8.05
SWITCHING FREQUENCY
8.06
LOW WATER LEVEL ALARM ACTIVE
8.07
LOW WATER ALARM LIMIT
8.08
PRIMING TIME
VALUES
Units.
Default
Min.
OFF
M-Su
M-F
OFF
S-Su
M, T,X,T,F,S,Su
Same as parameter 7.07 for program 2.
Same as parameter 7.08 for program 2.
8. PARÁMETROS AVANZADOS
VALUES
Units.
Default
Min.
Hz
2800
1400
Bar
Bar
Bar
10
5
Bar
2.5
2
KHz
7.7
2,5
ON
ON
%
75
50
min
2
1
29
Max.
This parameter is visible only if one of the 2 clock
options is selected in the previous parameter.
It enables the days or the block of days to be
programmed, such as M-Su that refers to Monday
through Sunday, in which the relay is to be activated.
Max.
3400
Modifies the maximum speed of pump operation.
You can modify the units to represent the pressure of
PSI
the installation.
Enables you to adjust the range of detection of the
58
transducer if its scale is not the standard 4-20 mA
(0-10 Bar).
In this point, indicate the maximum pressure that
the filter supports, so that in normal operation the
5
inverter takes it into account and acts accordingly so
that this pressure is never exceeded.
Enables you to modify the switching frequency of the
variator, reducing the noise, although uncommon,
of the switching at the expense of an increase in
16
temperature of the electronics.
N.B. We do not recommend modifying the
default value except when expressly indicated
by the Technical Department.
Enables the constant monitoring of the pump
OFF
running dry, if this occurs.
Value used in the mathematical algorithm that
90
calculates the pump running dry.
During the priming time, the detection of running dry
10
will not be operative even though the monitoring is
enabled.
EN
Notes