Additional functions
Adjustable low flow
cut-off (SMU)
Limit-value
monitoring
Mains version
Power supply
Calculation cycle
Backup battery
Low-voltage power supply for flow transmitter
Supply voltage
Flow transmitter
90
Function for stopping the energy calculation when
the temperature difference is too low,
ΔT SMU adjustable ΔT = 0 - 2.99 K
One-sided or two-sided, hysteresis 0 - 10%,
action of the output signal is selectable
100 - 240 V AC, 50/60 Hz, max. 5W (in accordance
with EN 1434)
12 - 42 VDC oder 12 - 36 VAC, max. 1 VA (acc. EN
1434)
At supply via adapter « insulated supply 24V-24V»
(Art.-Nr. 80828):
24 VDC ±20%, max. 7 Watt (at adapter)
1 s
3.6 V lithium battery
Terminals 108/ 109
(depending on the version)
24 VDC, max.150 mA,
el. isolation max. 48V V DC
e.g. AMFLO
MAG Smart
®
or active sensors
Terminals 106/ 107
3.6 VDC, max. 2 mA
e.g. AMFLO
SONIC
®
UFA 113
CALEC
®