7 Programming

In order to adapt the unit to a particular application, the HDA 5500 is programmed by varying
the basic settings. The basic settings are combined in a menu.
Important:
When the menu is activated, no switching operations are carried out.

7.1 Adjusting the basic settings

To change the basic settings, the menu must be activated.
Procedure for activating the menu:
During normal operation, press the MODE key and hold down for at least 5 s.
MEnu (Menu) is displayed.
After approximately 2 s the display changes and the first menu point is displayed (varies
according to type).
Press MODE until the required menu point appears in the display.
After approximately 2 s the display changes and the actual setting is displayed.
Use
or
to change the setting.
Press MODE again until the next required menu point appears in the display.
mode
≥ 5 s
Press Mode key and hold
down until Menu appears
Procedure for adopting and storing changes and to close the menu:
Press MODE until the menu point End is displayed.
After approximately 2 s the display changes and No is displayed.
Use
or
to change the setting to Yes.
Confirm with MODE.
If the basic settings have been changed and the menu has been closed with Yes, then for
approximately 2 s ProG (Programming) is displayed when leaving the menu. The changed
settings are then saved in the HDA 5500. Afterwards the display returns to normal operation.
Important:
If no key is pressed for longer than approximately 25 s, then the menu automatically closes
down. Any changes which may have been made will not be adopted or saved.
Menu is displayed
Press mode key until
Release mode key