1.5.1 Maximum pressure limitation
with external interlock
When the interlock circuit shown above is used, the requirements according to DIN 57116/VDE 0116
are fulfilled if the electrical plant, such as contactors or relays, correspond to the external interlock
circuit VDE 0660 or VDE 0435 respectively.
DWR = pressure monitor
T1
= STOP
T2
= START
S
= signal
(as required)
K1
= relay with
self-hold
Safety
circuit
1.5.2 Minimum pressure limitation
with external interlock
DWR = pressure monitor
T1
= STOP
T2
= START
S
= signal
(as required)
K1
= relay with
self-hold
Safety
circuit
33