Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

8.1. User variables:

MODBUS Point Type: HOLDING REGISTER
Read command: 03 (03Hex)
Write command: 16 (10Hex)
Address
write/read Description
User Working Mode:
16430
0 = Cool; 1 = Heat; 2 = Auto
On Off Status (Memorized into EEprom)
16431
0 = Off; 1 = On
Fan Control
16432
0 = Min; 1 = Med; 2 = Max; 3 = Auto
16433 Setpoint Cooling
16434 Setpoint Heating
16435 Profile 1: Start band 1
16436 Profile 1: End band 1
16437 Profile 1: Start band 2
16438 Profile 1: End band 2
16439 Profile 2: Start band
16440 Profile 2: End band
16441 Profile 1: Set Cool Band 1
16442 Profile 1: Set Cool Band 2
16443 Profile 2: Set Cool Band
16444 Profile 1: Set Heat Band 1
16445 Profile 1: Set Heat Band 2
16446 Profile 2: Set Heat Band
Monday Profile Selection
16447
1 = P1; 2 = P2; 3 = P3; 4 = P4
Tuesday Profile Selection
16448
1 = P1; 2 = P2; 3 = P3; 4 = P4
Wednesday Profile Selection
16449
1 = P1; 2 = P2; 3 = P3; 4 = P4
Thursday Profile Selection
16450
1 = P1; 2 = P2; 3 = P3; 4 = P4
Friday Profile Selection
16451
1 = P1; 2 = P2; 3 = P3; 4 = P4
Saturday Profile Selection
16452
1 = P1; 2 = P2; 3 = P3; 4 = P4
Sunday Profile Selection
16453
1 = P1; 2 = P2; 3 = P3; 4 = P4
Profile Enabled
16454
0 = Off; 1 = On
16460 Setpoint Fan CO2
16461 Setpoint Supply Fan Pressure
16462 Setpoint Return Fan Pressure
16480 Return speed correction
16481 Night Function enabled by keyboard
16482 Night: Start band
16483 Night: End band
16484 Night: Fan Speed [%]
16485 Night: Setpoint Cooling
16486 Night: Setpoint Heating
16500 Antifreeze Setpoint
16503 Defrost: Setpoint Expulsion Temperature
Fresh air temp. set point for automatic
16520
changeover
16521 Season changeover differential
firmware 1.03
Electronic Control "LC2" User Manual
Value
2
0
3
26.0
20.0
08:00
12:00
14:00
17:00
08:00
17:00
26.0
26.0
26.0
20.0
20.0
20.0
1
1
1
1
1
2
4
0
700
50
50
0
0
22:00
07:00
50
26.0
20.0
5.0
-4.0
15.0
10.0
Rev.11
Um
Default
2
0
3
°C
260
°C
200
HH:MM
480
HH:MM
720
Profile 1: Start band 1
HH:MM
840
HH:MM
1020
Profile 1: Start band 2
HH:MM
480
HH:MM
1020
Profile 2: Start band
°C
260
Profile 1: Set Heat Band 1
°C
260
Profile 1: Set Heat Band 2
°C
260
Profile 2: Set Heat Band
°C
200
°C
200
°C
200
1
1
1
1
1
2
4
0
ppm
Pa
Pa
%
0
0
HH:MM
1320
HH:MM
420
50
°C
260
°C
200
°C
50
°C
-40
°C
150
°C
100
Min
Max
0
2
0
1
0
3
50
350
50
350
0
Profile 1: End band 1
1439
0
Profile 1: End band 2
1439
0
Profile 2: End band
1439
350
350
350
50
Profile 1: Set Cool Band 1
50
Profile 1: Set Cool Band 2
50
Profile 2: Set Cool Band
1
4
1
4
1
4
1
4
1
4
1
4
1
4
0
1
500
2000
1
Pressure Full Scale Sensor
1
Pressure Full Scale Sensor
-50
50
0
1
0
1439
0
1439
0
100
50
350
50
350
-50
150
-150
100
300
50
1
200
EN 14/ 15
EN

Publicité

Table des Matières
loading

Table des Matières