5.8. Plant configuration ()
(password) 1
(Plant type)
0= 2 Pipes (unique changeover coil)
1= 2 Pipes + Heater (cooling coil + electrical post heater)
2*= 4 Pipes (cooling coil + heating coil)
(Inverter fan enable)
no - yes*
(Air flow control) reboot the controller after setting
0*=Temperature
1=CO2 (2000ppm)
2=Supply and exhaust pressure, 2 Probes (500Pa)
3=Supply air pressure (500Pa)
4= PIR (occupant sensor) + Temperature
(Antifreeze electric pre heater enable)
no* - yes
(Mixing damper enable)
0*= OFF
1= ON (with mixing dampers only)
2= CO2 digital sensor + ON-OFF dampers (DO1)
3= CO2 analog sensor + modulating dampers (AO3)
(Heat exchanger defrost management)
0*=Off or Only Mix Chamber
1=Preheating
2=Modulating Fan
(Regulation probe)
0* = AI1 (supply air)
1 = Display (SKW keyboard)
(Remote summer / winter changeover enable)
no* - yes
(Fire alarm managment)
0*= Off, in case of fire alarm the unit is completely stopped
1= On, in case of fire alarm the dampers are open and the fans run at max speed.
2= Available only with Fanl= yes: in case of fire alarm the dampers are open and only the return fans runs at max speed.
(Water coil antifreeze sensor enable)
no* – yes
(Modbus protocol address)
1*
(Modbus protocol
0-1-2= not used
3*= 9600 baud
4= 19200 baud
(Modbus protocol parity
1*= EVEN
2= NONE
3= ODD
(Alarm history reset)
no
(Password)
1*
* Default value
¹
To apply the changes protocol reboot the controller
firmware 1.03
Electronic Control "LC2" User Manual
¹
Baudrate) ¹
) ¹
¹
Rev.11
EN
EN 7/ 15