Operating Instructions And Parts Manual
supplied with a grounding conductor
4. Fill sump with water. The pump will
and grounding type attachment plug.
start automatically when the water
Use a grounded receptacle to reduce
has filled the sump to a depth of
the risk of fatal electrical shock.
approximately 13". The pump will
stop when the water depth is
Never cut off the round grounding
approximately 7". The pump will
prong. Cutting the cord or plug will
recycle thereafter as required.
void the warranty and make the pump
inoperable.
5. Do not operate the pump unless it is
submerged in water. Dry running
2. This pump is only for use on 120
causes pump failure.
Volt (single-phase), 60 hz, 15 amp
service and is equipped with a 3-
6. The motor is equipped with an
conductor cord and 3-prong,
automatic reset thermal protector.
grounding type plug. Insert the
7. While the pump is draining the pit,
float switch cord plug directly into
verify that the discharge piping is
a 120 volt outlet.
carrying the water to a point several
3. Insert the pump power cord plug
feet away from the foundation.
directly into the back of the float
8. If pump discharge line is exposed to
switch cord plug (See Fig. 2).
freezing temperature, the exposed
line must be pitched to drain.
Grounding
Grounded
Trapped water will freeze and
Blade
Outlet
damage the pump.
Maintenance
TEST
RESET
DANGER
!
Power
Cord
Always disconnect the
electrical supply before
Switch
attempting to install,
Cord
Figure 2
service, relocate or
perform any maintenance. If the power
source is out of sight, lock and tag in
Troubleshooting Chart
Symptom
Possible Cause(s)
Pump will not start
1. Blown fuse
or run
2. Low line voltage
3. Defective motor
4. Defective float switch
5. Impeller
6. Float obstructed
Pump starts and
1. Backflow of water from
stops too often
piping
2. Faulty float switch
Pump will not shut
1. Defective float switch
off or thermal
2. Obstacle in piping
protector turns off
3. Float obstructed
Pump operates but
1. Low line voltage
delivers little or no
2. Plugged impeller
water
www.waynewatersystems.com
the open (off) position to prevent
unexpected power application. Failure
to do so could result in fatal electrical
shock. Only qualified electricians
should repair this unit. Improper repair
could result in fatal electrical shock.
1. Let the pump cool for a minimum
of two hours before servicing
because the pump contains hot oil
under pressure and the motor is
hot.
2. Disassembly of the motor prior to
expiration of warranty will void the
warranty. If repairs are required,
see troubleshooting chart.
4. Inlet should be kept clean and free
of all foreign objects and inspect
annually. A clogged inlet will
damage pump.
5. Pump should be checked monthly
for proper operation.
This pump contains
WARNING
!
dielectric oil for
cooling. This oil can be harmful to the
environment. Check the state
environmental laws before disposing
this oil.
Corrective Action
1. If blown, replace with proper sized fuse or reset breaker.
2. If voltage is under 108 volts, check wiring size.
3. Replace pump
4. Replace float switch
5. If impeller will not turn, remove housing and remove blockage
6. Make sure float move freely up and down
1. Install or replace check valve (Wayne No. 66005-WYN)
2. Replace float switch
1. Replace float switch
2. Remove pump and clean pump and piping
3. Make sure float moves freely up and down
1. If voltage is under 108 volts, check wiring size.
2. Clean out impeller
2
Instructions D'Utilisation Et Manuel De Pièces
Liste De Pièces De Rechange
Pour Les Pièces De Rechange, composer 1-800-237-0987
Utiliser seulement les pièces de
l'usine pour la réparation de cette
S'il vous plaît fournir l'information suivante:
-Numéro du Modèle
pompe.
-Numéro de Série (si présent)
-Description et numéro de la pièce
Nº de
Réf.
1.
2.
3.
4.
5.
3
4
5
Spécifications
Exigences d'alimentation ................120V, 60 Hz
Moteur ..............................................Monophasé, rempli d'huile
Puissance...........................................1/3 HP (CDT33, SPT33, SSPT33)
...........................................................1/2 HP (CDT50, SPT50, SSPT50)
Gamme de température liquide .....40°F à 120°F
Exigences de circuit..........................15 A (min)
Dimensions .......................................11
1
/
po H x 9
3
/
po base
2
4
Niveau de démarrage (réglé à l'usine)..13 po
Niveau d'arrêt (réglé à l'usine) .......7 po
Correspondance:
Wayne Water Systems
101 Production Drive
Harrison, OH 45030
Numéro de Pièces pour Modèles
CDT33
SPT33, SPT50
Description
CDT50
SSPT33, SSPT50
Néc. d'interrupteur flotteur
60022-001
60022-001
Néc. de couvercle supérieur
60030-001
60030-001
Plaque de Turbine
15958
Turbine
60000-001
60000-001
Volute
60016-001
60007-001
2
1
5
Models SPT33, SPT50,
SSPT33, and SSPT50
Fabrication
Carter de moteur .............Acier laminé à froid
Volute ...............................Fonte (CDT33, CDT50)
..........................................Thermoplastique renforcé
de verre
(SPT33, SPT50, SSPT33, SSPT50)
Turbine .............................Thermoplastique renforcé
de verre
Arbre.................................Acier cémentation
Joints.................................Buna N
Décharge ..........................1
1
/
po NPT
2
Couvercle de moteur .......Thermoplastique renforcé
de verre
3 Fr
15958