REFRIGERANT PIPING

4
3. REFRIGERANT PIPING

3.1. PIPING CONNECTION

3.1.1. PIPING POSITION
3.1.2. SIZE OF PIPING CONNECTION
In case of R407C / R410A
Model RPF(I)
1.0 / 1.5
∅12.70 (5/8)
Gas Piping
∅ 6.35 (1/4)
Liquid Piping
∅ 18,5 OD
Drain Piping
Special instructions for R410A
As R410 pressure is about 1.4 times higher than R407C,
improper installation may cause a serious trouble.
It is necessary to use the copper pipes, size of flare pipe ends
and flare nuts as shown below.
Thickness of Copper Pipes
Nominal
Outer
Diameters
Diameters
1/4
6.35
3/8
9.53
1/2
12.70
5/8
15.88
(mm)
2.0
2.5
∅15.88 (5/8)
∅15.88 (5/8)
∅ 6.35 (1/4)
∅ 9.53 (3/8)
∅ 18,5 OD
∅ 18,5 OD
(mm)
R407C
R410A
0.80
0.80
0.80
0.80
0.80
0.80
1.00
1.00
Flare Pipe Dimensions
Nominal
Diameters
1/4
3/8
1/2
5/8
Flare Nut Dimensions
Nominal
Diameters
1/4
3/8
1/2
(mm)
A
Outer
+0/-0.4
Diameters
R407C
R410A
6.35
9.0
9.1
9.53
13.0
13.2
12.70
16.2
16.6
15.88
19.4
19.7
(mm)
B
Outer
Diameters
R407C
R410A
6.35
17
17
9.53
22
22
12.70
24
26