According to UL 60947-4-1
Use wire Cu 75℃ only.
100(S)-E190, 100(S)-E205: Use Pressure Terminal Connectors ILSCO D-3608 (Allen Bradley ref 100-ETL205) or use Listed (ZMVV/7) Wire
Connectors and Soldering Lugs. Wire connectors (Cable pole-shoe) crimped with special factory tool. Enclosure
with min dimension 24 by 20 by 10 inches should be used. Suitable for use on a circuit capable of delivering not more
than the max symmetrical amperes at the max voltage shown in table 1 and 3 below.
100(S)-E265, 100(S)-E305, 100(S)-E370, 300(S)-FO: Use Pressure Terminal Connectors ILSCO D-3615 (Allen Bradley ref 100-ETL370) or use Listed (ZMVV/7)
Wire Connectors and Soldering Lugs. Wire connectors (Cable pole-shoe) crimped with special factory tool. Enclosure
with min dimension 36 by 30 by 12 inches should be used. Suitable for use on a circuit capable of delivering not more than
the max symmetrical amperes at the max voltage shown in table 2 and 4 below.
Type 1
100(S)-E190, 100(S)-E205
Circuit Breaker A
Fuse A/Class
Max Short Circuit Current at 208-240V (kA)
Max Short Circuit Current at 480V (kA)
Max Short Circuit Current at 600V (kA)
100(S)-E265, 100(S)-E305, 100(S)-E370, 300(S)-FO
Circuit Breaker A
Fuse A/Class
Max Short Circuit Current at 208-240V (kA)
Max Short Circuit Current at 480V (kA)
Max Short Circuit Current at 600V (kA)
Type 2
100(S)-E190, 100(S)-E205
Circuit Breaker A
Fuse A/Class
Max Short Circuit Current at 480V (kA)
Max Short Circuit Current at 600V (kA)
100(S)-E265, 100(S)-E305, 100(S)-E370, 300(S)-FO
Circuit Breaker A
Fuse A/Class
Max Short Circuit Current at 480V (kA)
Max Short Circuit Current at 600V (kA)
For applications above 690V, terminal shrouds 100-ETS205L or 100-ETS370L should be used.
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 100-IN038D-EN-E June, 2021
Table 1
140G-K/J
140G-K3
400/RK5
400/J
10
100
100
10
100
35
10
100
25
Table 2
140G-M
140G-M5 140G-M6 140G-M0
800/L
600/J
10
100
100
18
100
50
25
18
100
Table 3
140G-K
140G-K6
350/J
400/J
100
65
10
100
35
10
Table 4
140G-M
140G-M6
600/J
600/J
100
18
65
100
18
35
140G-K6
140G-K0
140G-K15
140G-J2
100
100
100
65
100
100
35
65
100
100
100
65
100
35
42
Breaking all lines. Max 600V AC, 50/60 Hz:
Herm ref comp, AC-8a
TYPE
LRA
FLA
1400
200
100(S)-E190
100(S)-E205
250
1500
100(S)-E265
300
2100
100(S)-E305
350
2450
100(S)-E370
520
3120
300(S)-FO
300
2100
DIR 10002941910 (Version 04)
Copyright © 2021 Rockwell Automation, Inc. All Rights Reserved. Printed in Sweden.
140G-J6
140G-J3
140G-J0
65
100
100
100
25
35
65
100
18
22
25
Ballast, AC-5a/
Elevator duty
Resistance air heating
77
250
300
99
125
400
450
149
156
520
400
125
4/4
50