Fault
Countermeasure
Fan doesn't
 Check that the mains fuse
start up
 Get a trained electrician to
or
Motor hums
or
Operating
 Only use fuses with rating
indicator light at
the 5-step
transformer =
G fuse links
Off
– TRE 0,4-1: T 0.5/250
– TRE 0,6-1: T 0.8/250
– TRE 1,6-1: T 2.0/250
– TRE 3,3-1: T 4.0/250
– TRE 6,5-1: T 8.0/250
– TRE 10-1: T 12.5/250
– TR 0,4-1:
– TR 0,8-1:
– TR 2,5-1:
– TR 6,6:
– TRV 1,0-1: T 1.25500
– TRV 1,7-1: T 2.0/500
– TRV 2,5-1: T 3.15/500
– TRV 5,0:
D fuse links
for TRV 11:
D01 16 A/400 (Load)
D01
Table 3: Fault rectification 1
Fault
Countermeasure
TRV-
The TRV.. transformer
transformers
interrupts the power supply
Fan's thermal
to the fan if the fan's thermal
overload
overload protection is
protection has
triggered.
triggered.
Fan stopped,
operating
indicator light =
Off
Table 4: Fault rectification 2
is switched on.
check the unit fuse in the
transformer and replace it
as necessary.
data as shown below.
T 0.5/500
T 1.0/500
T 3.15/500
T 8.0/500
T 6.3/500
2 A/400 (Controller)
Switch down to speed
setting "0".
Let the motor cool down.
Cool-down time can be up
to 60 minutes.
Set the required speed
level.
10. Dismantling
Danger to life. Unit is powered
up
 Switch the mains fuse off.
DANGER
 Position a visible warning
notice to avoid the unit being
accidentally switched back on.
Dismantling should only be carried out
i
by a trained electrician.
In the case of housing type
i
the threaded inserts as shown below.
11. Disposal
Not in domestic waste.
i
The unit contains in part material that
can be recycled and in part
substances that should not end up as
domestic waste.
 Dispose of the unit once it has reached the
end of its working life according to the
regulations valid in your country.