DRB480-xx-1 Handbook
DRB-480 Handbook
11. Phase to phase operation
The DRB480 is protected by an internal fuse in the Live line. When connecting the DRB480 between two phases of a
three phase system an external fuse or circuit breaker must be used in the Neutral line (N). This is to protect against
a fault between the now 'live' Neutral line and Earth. See section 12 for external protection requirements." Note:
The phase-to-phase supply must not exceed the safety approval input voltage of 100-240VAC+10% and 20A Max
branch circuit current.
OUTPUT
INPUT
PE
Fuse
L1
100-240VAC/20A
L2
MAX
L3
12. External Fuse Rating
If required a 250Vac/10A rated fuse should be fitted externally on the input line. Surge current flows when line
turns on. Use slow-blow fuse or time-lag type fuse. Do not use fast-blow fuse. Fuse rating is specified by in-
rush current value at line turn-on. Do not select the fuse according to input current (RMS.) values under the
actual load condition.
Page 19 of 22
DC
Internal Fuse
Live(L) line
AC
N
L
260235 Rev 5, June 2020