12 Device information
1
Type and order code
2
Design
Heat source
2.1
Model
2.2
Controller
2.3
Thermal energy metering
2.4
Installation location
2.5
Performance level
3
Operating limits
3.1
Heating water flow / return
Cooling water flow
Air (heating)
Air (cooling)
Brine (heating)
4
Flow / sound
4.1
Heating water flow rate / internal pressure differential
in accordance with 14511
minimum
4.2
Minimum cooling water throughput /internal pressure differential
4.3
Brine flow rate / internal pressure differential
4.4
Sound power level according to EN 12102Normal mode / lowered operationdB(A)
4.5
Sound pressure level at a distance of 10 m (air outlet side)
Normal operation / reduced operation
4.6
Air flow (controlling range EC fan)
5
Dimensions, weight and filling quantities
5
5.1
Device dimensions
5.2
Weight of the transportable unit(s) incl. packaging
5.3
Device connections for heating
5.4
Device connections for brine
5.5
Refrigerant / total filling weight
5.6
Lubricant / total filling quantity
5.7
Volume of heating (cooling) water in device
6
Electrical connection
6.1
Supply voltage / fuse protection
6.2
Control voltage / fusing via WPM
6.3
FI circuit breaker / category
6.4
Degree of protection according to EN 60 529
6.5
Starting current limiter
6.6
Rotary field monitoring
6.7
Starting current
6.8
Nominal power consumption A7/W35 / max. consumption
Nominal current A7/W35 / cos
6.9
6.10 Power consumption of compressor protection (per compressor)
6.11 Power consumption of fan
7
Complies with the European safety regulations
8
Additional model features
8.1
Type of defrosting
8.2
Condensate tray frost protection / Water in device is protected from freezing
8.3
max. operating overpressure (heat source / heat sink)
8.4
Hydraulic 4-way reversing valve (external)
www.glendimplex.de
A7/W35-30
m³/h / Pa
A7/W45-40
m³/h / Pa
A7/W55-47
m³/h / Pa
m³/h / Pa
3
m³/h / Pa
m³/h / Pa
4
dB(A)
H x W x L mm
inches
inches
type / kg
type / litres
water / brinelitres
6
A / ---
2
452167.66.02 · FD 9509
Reversible with mode for two heat sources
°C
°C
°C
°C
°C
m³/h
kg
A
kW
W
kW
8
bar
LSA 60TUR
LSA 60TUR
Air & brine
WPM wall-mounted
no
Outdoors
2
1
up to 60
±2 / from 18
2
+6
to +20
-20 to +40
+15 to +45
flow
return
+5
to +25
10.5 / 6500
10.2 / 6200
6.2 / 2300
5.3 / 1700
10.8 / 6900
11.0 / 32500
up to 74 / up to 70
up to 45 / up to 41
10000 - 22000
2300 x 2110 x 1000
1090
R 2"
R 2"
R417A / 33.0
Polyolester (POE)/7.2
18.8 / 12.0
3~/PE 400V (50Hz) / C50A
1~/N/PE 230V (50Hz) / 4 ET
Yes / A
IP 24
Soft starter
No
78
14.75 / 29.9
28.8 / 0.8
70, thermostatically controlled
up to 3.1
7
Reverse circulation
Ja
3.0
Accessories (recommended)
EN-10