5
Electrical connection
2
Function switch position ON
Reinitialisation ON-OFF/ OFF-ON
No function
No function
Servo drive direction and position
feedback signal 100..0%
2.. 10 V DC
Valve blocking protection On
Factory setting: Switches 1-6 OFF; Closed 100 % / Open 0 %
Switch 1 (only for 24 V): Valve blocking protection - If system conditions allow, valve
blocking protection can be activated during commissioning. Blocking protection prevents
the cone from sticking when the valve has not been in operation for a longer period of time,
e.g. when the cold water circulation has not yet been started. When blocking protection is
activated, the valve cone is lifted for a few seconds if there has been no lifting movement
within 21 days.
Switch 2 (only for 24 V): Setting the control range of the continuous control signal 0..10 V
DC or 2..10 V DC (see table on page 24).
Switch 3 (only for 24 V): Setting of servo drive direction and position feedback for control
voltage 10 V DC „Valve open"
Switch 6: Reinitialisation - If the valve is reinstalled, it must be taught in again through rei-
nitialisation. This is done by changing the position of switch 6 from „OFF" to „ON" or from
„ON" to „OFF". During initialisation, the LED under the access cover flashes and the stroke
scale moves. After a full positioning run (9 mm), reinitialisation is completed by resetting
switch 6.
© www.kemper-olpe.de – 06.2020 – K410061500001-00 – 25/72
Switch
Factory setting: OFF
Factory setting: 0..10 V DC
or „Valve closed"
Factory setting: 0..100%, „Valve open"
Factory setting: OFF
Function switch position OFF
Reinitialisation ON-OFF/ OFF-ON
No function
No function
Servo drive direction and position feed-
back signal 0..100%
0.. 10 V DC
Valve blocking protection Off
.